| 2023-03-06 10:05:48 | ******THE PREVIOUS FIRE COMMENTS HAVE NOT BEEN |
| | ADDRESSED**** |
| | |
| | PLEASE PROVIDE THE FINISHED FLOORING PRODUCT NAME AND |
| | SPEC SHEETS. |
| | |
| | THE PREVIOUS FIRE COMMENTS ARE RESUBMITTED BELOW: |
| | |
| | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE |
| | MARSHAL, WITH THE FOLLOWING COMMENTS: |
| | |
| | 1) THERE IS AN INDICATION OF THE SPEC SHEET FOR THE |
| | FLOOR UNDERLAYMENT, BUT NO SPEC SHEET NOR A PRODUCT |
| | NAME FOR THE ACTUAL PROPOSED ENGINEERED WOOD FLOORING. |
| | |
| | ENGINEERED WOOD FLOORING IS MANUFACTURED AROUND THE |
| | WORLD BUT NOT ALL ARE TESTED AND MEETING LISTED AND |
| | NFPA STANDARDS. |
| | |
| | PER NFPA 101, CH 30 |
| | |
| | 30.3.3.3 INTERIOR FLOOR FINISH. |
| | 30.3.3.1 GENERAL. INTERIOR FINISH SHALL BE IN |
| | ACCORDANCE WITH |
| | SECTION 10.2. |
| | |
| | 10.2.7.2* FLOOR COVERINGS, OTHER THAN CARPET FOR WHICH |
| | 10.2.2.2 |
| | ESTABLISHES REQUIREMENTS FOR FIRE PERFORMANCE, SHALL |
| | HAVE A |
| | MINIMUM CRITICAL RADIANT FLUX OF 0.1 W/CM2. |
| | |
| | FOR THE OFFICIAL RECORD, PLEASE PROVIDE THE ENGINEERED |
| | WOOD FLOORING NAME AND THE PRODUCT SPEC SHEETS |
| | INDICATING THE FIRE BEHAVIOR RATING. |
| | |
| | IF THE PROPOSED FLOORING IS PORCELAIN/CERAMIC TILE, |
| | NATURAL STONE TILE, CONCRETE TILES, PRODUCT SPEC SHEETS |
| | WOULD NOT BE REQUIRED. |
| | |
| | PRODUCT SPEC SHEETS ARE REQUIRED FOR LVT, VINYL |
| | FLOORING, WOOD/VINYL LAMINATES, ENGINEERED WOOD, ETC. |
| | |
| | |
| | |
| | 2) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET |
| | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE |
| | ABOVE. |
| | |
| | |
| | 3) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE |
| | RE-SUBMITTAL OF THE ABOVE. |
| | |
| | |
| | PETER LEDUC |
| | FIRE MARSHAL |
| | 561-804-4709 |
| | [email protected] |
| | |