| 2023-03-24 07:05:56 | 1ST REVIEW FBC-2020 RES. FUEL GAS |
| | PERMIT- 23021382 |
| | 3/24/2023 |
| | |
| | CODES IN EFFECT: |
| | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION |
| | 2020 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. PLEASE REVIEW THE COMMENTS |
| | AND NOTE THAT GAS FOR THE GENERATOR CAN BE UNDER A |
| | SEPARATE PERMIT BY REQUEST. |
| | |
| | 1) A GAS RISER DRAWING IS REQUIRED PER SEC. 107.3.5.3 |
| | WPB. PROVIDE A COMPLETE GAS RISER DRAWING THAT INCLUDES |
| | THE NEW PIPING TO THE GENERATOR AND THE EXISTING THE |
| | GAS PIPING AND APPLIANCES AT THE RESIDENCE- SECTION |
| | G2412.3 & G2412.4 FBC RES. REFER TO FBC RES. CHAPTER 24 |
| | FUEL GAS- THE RISER SHALL INDICATE: |
| | A) TYPE OF GAS- NATURAL OR LP. |
| | B) DELIVERY PRESSURE AT THE METER. |
| | C) TOTAL BTU LOAD AND INDIVIDUAL APPLIANCE BTU LOADS. |
| | D) TYPES AND SIZES OF PIPING. |
| | E) TOTAL DEVELOPED LENGTH OF THE SYSTEM FROM THE METER |
| | TO THE MOST REMOTE APPLIANCE OUTLET. |
| | F) BRANCH AND CUT PIPE LENGTH MEASUREMENTS. |
| | G) LOCATIONS OF REGULATORS AND OUTLET PRESSURES. |
| | H) LOCATIONS OF SHUT OFF VALVES. |
| | I) PIPE SIZING TABLES |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |