| Notes |
| Date |
Text |
| 2023-03-23 18:54:16 | RESIDENTIAL (R3)BUILDING REVIEW COMMENTS | | | CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS. | | | PERMIT #23021382 | | | 10241 HERONWOOD LN | | | | | | 1- REVISE NOTE ON SURVEY. THE GENERATOR SHALL BE | | | LOCATED A MINIMUM OF 10 FT. FROM AIR INTAKES INTO THE | | | BUILDING- SEC. R303.5.1 FBC RES. PLEASE CORRECT THE | | | NOTE INDICATING 5 FT. | | | | | | 2- GENERATOR CONCRETE PAD ENGINEERING HAS A COPY OF THE | | | ENGINEER'S DIGITAL SIGNATURE. NEED ORIGINAL | | | SEAL/SIGNATURE WHEN SUBMITTED FOR PUBLIC RECORDS. | | | ELECTRONIC SUBMITTALS NEED VERIFIABLE DIGITAL | | | SIGNATURE. | | | | | | ENGINEERS | | | 61G15-23.004 PROCEDURES FOR DIGITALLY SIGNING AND | | | SEALING ELECTRONICALLY TRANSMITTED PLANS, | | | SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS. | | | | | | WHEN RESUBMITTING, A TRANSMITTAL LETTER LISTING THE | | | ORIGINAL REVIEW COMMENT WITH A DESCRIPTION OF WHERE AND | | | HOW THE COMMENT WAS ADDRESSED WILL HELP TO EXPEDITE THE | | | REVIEW PROCESS. THANK YOU FOR YOUR ANTICIPATED | | | COOPERATION. | | | | | | PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY | | | QUESTIONS REGARDING THESE COMMENTS, | | | JULIO GOMEZ | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | DEVELOPMENT SERVICES DEPARTMENT | | | BUILDING DIVISION | | | (561)805-6712 | | | [email protected] |
|