2023-03-16 11:03:101ST REVIEW FMC
 PERMIT: 23021376
  
 CODES IN EFFECT: 2020
  
 FBC- FLORIDA BUILDING CODE
 FMC- FLORIDA MECHANICAL CODE
 FEC- FLORIDA ENERGY CONSERVATION
 FGC- FLORIDA FUEL GAS
 FEX- FLORIDA EXISTING BUILDING CODE
 FRC- FLORIDA RESIDENTIAL BUILDING CODE
 F.S.- FLORIDA STATUTES
 FAC- FLORIDA ACCESSIBILITY CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THE OUTDOOR AIR CALCULATIONS SHOULD SHOW THE OUTDOOR
 AIR REQUIRED FOR EACH RTU. REVISE THE OUTDOOR AIR
 CALCULATIONS TO SHOW THE ADDITIONAL RTU THAT WAS ADDED
 AND THE OUTDOOR AIR REQUIRED FOR EACH RTU. FMC
 403.3.1.1
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  