2023-03-21 08:53:06FIRE PROVISO COMMENT:
  
 NFPA 96, CHAPTER14.7.9 HOSE PROTECTION.
  
 14.7.9.1 SOLID FUEL APPLIANCES WITH FIREBOXES EXCEEDING
 0.14M3 (5 FT3) SHALL BE PROVIDED WITH A FIXED WATER
 PIPE SYSTEM WITH A HOSE IN THE KITCHEN CAPABLE OF
 REACHING THE FIREBOX.
  
 14.7.9.1.1 THE HOSE SHALL BE EQUIPPED WITH AN
 ADJUSTABLE NOZZLE CAPABLE OF PRODUCING A FINE TO MEDIUM
 SPRAY OR MIST.
  
 14.7.9.1.2 THE NOZZLE SHALL BE OF THE TYPE THAT CANNOT
 PRODUCE A STRAIGHT STREAM.
  
 14.7.9.2 THE SYSTEM SHALL HAVE A MINIMUM OPERATING
 PRESSURE OF 275.8 KPA (40 PSI) AND SHALL PROVIDE A
 MINIMUM OF 19 L/MIN (5 GPM).
  