| Plan Review Notes For Permit 23021330 |
| Permit Number |
23021330 |
|
| Review Stop |
FIRE |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2023-03-21 08:53:06 | FIRE PROVISO COMMENT: | | | | | | NFPA 96, CHAPTER14.7.9 HOSE PROTECTION. | | | | | | 14.7.9.1 SOLID FUEL APPLIANCES WITH FIREBOXES EXCEEDING | | | 0.14M3 (5 FT3) SHALL BE PROVIDED WITH A FIXED WATER | | | PIPE SYSTEM WITH A HOSE IN THE KITCHEN CAPABLE OF | | | REACHING THE FIREBOX. | | | | | | 14.7.9.1.1 THE HOSE SHALL BE EQUIPPED WITH AN | | | ADJUSTABLE NOZZLE CAPABLE OF PRODUCING A FINE TO MEDIUM | | | SPRAY OR MIST. | | | | | | 14.7.9.1.2 THE NOZZLE SHALL BE OF THE TYPE THAT CANNOT | | | PRODUCE A STRAIGHT STREAM. | | | | | | 14.7.9.2 THE SYSTEM SHALL HAVE A MINIMUM OPERATING | | | PRESSURE OF 275.8 KPA (40 PSI) AND SHALL PROVIDE A | | | MINIMUM OF 19 L/MIN (5 GPM). | | | | | | C. WALKER | | | | | | 561-804-4762 | | | | | | [email protected] | | | |
|