| Plan Review Notes For Permit 23021329 |
| Permit Number |
23021329 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2023-03-08 08:33:58 | 1ST REVIEW FMC | | | PERMIT: 23021329 | | | | | | CODES IN EFFECT: 2020 | | | | | | FBC- FLORIDA BUILDING CODE | | | FMC- FLORIDA MECHANICAL CODE | | | FEC- FLORIDA ENERGY CONSERVATION | | | FGC- FLORIDA FUEL GAS | | | FEX- FLORIDA EXISTING BUILDING CODE | | | FRC- FLORIDA RESIDENTIAL BUILDING CODE | | | F.S.- FLORIDA STATUTES | | | FAC- FLORIDA ACCESSIBILITY CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) THE PERMIT APPLICATION STATES - INSTALL 3 HOODS WITH | | | KITCHEN COOL. THE MASTER FOR THIS PROJECT ALREADY SHOWS | | | A MECHANICAL SYSTEM TO COOL THE KITCHEN. IS THIS | | | KITCHEN COOL THE MAKEUP AIR FOR THE HOODS? COOLING THE | | | KITCHEN IS DIFFERENT FROM MAKE UP AIR FOR THE HOODS. | | | PLEASE SHOW A SIZING CALCULATION FOR THE 10 TON KITCHEN | | | COOLING UNIT. ALSO, PROVIDE THE UPDATED AIR BALANCE | | | REPORT WHICH WOULD INCLUDE KEF-2. FMC 508.1 | | | | | | 2) PROVIDE A ROOF PLAN SHOWING THE CLEARANCES FROM THE | | | ROOF EDGE IS A MINIMUM OF 10 FOOT OR PROVIDE THE GUARD | | | PROTECTION. FMC 304.11 | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM. | | | | | | MICHAEL EDWARDS | | | MECHANICAL EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL. 33401 | | | 561-805-6728 | | | [email protected] | | | |
|