| Plan Review Notes For Permit 23021319 |
| Permit Number |
23021319 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2023-03-29 13:50:22 | FLORIDA BUILDING CODE 2020 7TH EDITION | | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED | | | NFPA 70 2017 EDITION | | | | | | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW | | | | | | 1. PROVIDE LOAD CALCULATION, INCLUDE EXISTING AND NEW | | | LOADS TO CONFIRM CAPACITY OF SERVICE IS ADEQUATE. | | | NEC 220 | | | | | | 2. PROVIDE INFORMATION OF THE ELECTRICAL PANEL (RATING | | | AND PROTECTION) WHERE THESE LOADS ARE CONNECTED ALONG | | | WITH THE PANEL SCHEDULE. NEC 240, 408.4(A) | | | | | | END OF COMMENTS | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM. | | | | | | RUBEN PEREZ PERDOMO, P.E. | | | ELECTRICAL PLANS EXAMINER | | | 561-805-6738 | | | [email protected] | | | |
|