| 2023-04-03 15:11:20 | 1ST REVIEW FBC-2020 PLUMBING |
| | PERMIT-23021308 |
| | 4/3/2023 |
| | |
| | CODES IN EFFECT: |
| | FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 |
| | FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) SHEETS P1.1 & P3.1: THE URINAL FIXTURE DRAIN CANNOT |
| | CONNECT TO THE 3-INCH HORIZONTAL WET VENT FOR THE |
| | BATHROOM FIXTURES- SEC. 202 & 912.1 FBC P. RELOCATE THE |
| | DRAIN CONNECTION EITHER UPSTREAM OR DOWNSTREAM OF THE |
| | WET VENT. |
| | |
| | 2) P2.1 & P3.1: THE THERMOSTAT CONTROL ON THE WATER |
| | HEATER CANNOT BE THE LIMITING DEVICE FOR HOT WATER |
| | DELIVERY. PLEASE PROVIDE A DETAIL FOR A LIMITING DEVICE |
| | FOR THE PURPOSE OF HOT WATER DELIVERY. THIS CAN BE |
| | ACCOMPLISHED BY INSTALLING A MASTER THERMOSTATIC MIXING |
| | VALVE AT THE WATER HEATER. THIS WOULD BE IN ADDITION TO |
| | THE REQUIREMENTS FOR TEMPERED WATER FOR PUBLIC |
| | HAND-WASHING- SEC. 607.1.1 FBC P. |
| | |
| | 3) P2.1 & P3.1: PROVIDE A THERMAL EXPANSION CONTROL |
| | DEVICE AT THE WATER HEATER- SEC. 607.3 FBC P. |
| | |
| | 4) P3.1: PROVIDE A PLUMBING FIXTURE SCHEDULE AND A |
| | EQUIPMENT SCHEDULE FOR THE WATER HEATER- SEC. 404.1 & |
| | 502.1 FBC P. |
| | |
| | 5) A4.01: PROVIDE THE FOLLOWING DETAILS IN COMPLIANCE |
| | WITH THE FBC ACC. |
| | |
| | A) CLEAR FLOOR SPACE DIMENSIONS FOR THE WATER CLOSETS- |
| | SEC. 604.3. |
| | |
| | B) CLEAR FLOOR SPACE DIMENSIONS FOR THE LAVATORIES- |
| | SEC. 606.2. |
| | |
| | C) TURNING SPACE DIAMETERS- SEC. 304.3. |
| | |
| | D) CENTERLINES OF THE ACCESSIBLE WATER CLOSETS FROM THE |
| | SIDE WALLS- SEC. 604.2. |
| | |
| | E) HEIGHTS OF THE WATER CLOSET SEATS FROM THE FINISHED |
| | FLOORS- SEC. 604.4. |
| | |
| | F) HEIGHTS OF THE LAVATORY SINK RIMS OR COUNTER |
| | SURFACES FROM THE FINISHED FLOORS- SEC. 606.3. |
| | |
| | G) HEIGHTS OF THE MIRRORS FROM THE FINISHED FLOORS TO |
| | THE REFLECTIVE SURFACES- SEC. 603.3 |
| | |
| | H) LOCATIONS, LENGTHS, AND MOUNTING HEIGHTS OF GRAB |
| | BARS FOR THE WATER CLOSETS- SECS. 604.5 & 609.4, |
| | FIGURES 604.5.1 & 604.5.2. |
| | |
| | I) CENTERLINES OF THE TOILET PAPER DISPENSERS MEASURED |
| | FROM THE FRONTS OF THE WATER CLOSETS- SECTION AND |
| | FIGURE 604.7. |
| | |
| | J) KNEE AND TOE CLEARANCES FOR THE LAVATORIES- SECTION |
| | 606.2 |
| | |
| | K) CLEAR FLOOR SPACE DIMENSIONS FOR THE WHEELCHAIR |
| | ACCESSIBLE DRINKING FOUNTAIN- SEC. 602.2. |
| | |
| | L) KNEE AND TOE CLEARANCES FOR THE WHEELCHAIR |
| | ACCESSIBLE DRINKING FOUNTAIN- SEC. 602.2. |
| | |
| | M) SPOUT HEIGHTS- SECS. 602.4 & 602.7. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |
| | CHRISTOPHER L. COLE |
| | MECHANICAL/PLUMBING PLANS EXAMINER |
| | 401 CLEMATIS STREET |
| | WEST PALM BEACH FL 33401 |
| | 561-805-6719 |
| | [email protected] |
| | |