| Plan Review Notes For Permit 23021306 |
| Permit Number |
23021306 |
|
| Review Stop |
P |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2023-04-03 17:06:26 | 1ST REVIEW FBC-2020 PLUMBING | | | PERMIT- 23021306 | | | 4/3/2023 | | | | | | CODES IN EFFECT: | | | FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 | | | FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020 | | | FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020 | | | FS- FLORIDA STATUTES | | | FAC- FLORIDA ADMINISTRATIVE CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) SHEET P0.1: PROVIDE A SCHEDULE FOR THE ACCESSIBLE | | | PLUMBING FIXTURES- SEC. 404.1 FBC P. PLEASE CLARIFY IF | | | THE TRANSFER TYPE ACCESSIBLE SHOWER IS A FACTORY MODULE | | | OR WILL BE SITE BUILT- SEC. 107.2.1 WPB. PLEASE INCLUDE | | | SHOWER PAN, CURB AND THRESHOLD DETAILS FOR ALL PROPOSED | | | NEW SHOWERS- SEC. 421.5.2 FBC P AND SEC. 608.7 FBC ACC. | | | | | | 2) P0.1: THE PLAN APPEARS TO SHOW SOME NEW DRAIN | | | PENETRATIONS THROUGH THE SLABS WILL BE REQUIRED. PLEASE | | | PROVIDE UL TESTED FIRESTOPPING DETAILS FOR ALL PIPE | | | PENETRATIONS- SEC. 315.1 FBC P. | | | | | | 3) A & P PLANS: PLEASE PROVIDE THE DIMENSIONS OF THE | | | STANDARD WATER CLOSET COMPARTMENTS- SEC. 405.3.1 FBC P. | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL/PLUMBING PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] |
|