| 2023-06-07 10:20:08 | RESIDENTIAL (R3) SECOND BUILDING REVIEW COMMENTS |
| | CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS. |
| | PERMIT #23021273 |
| | 292 SUMMA ST |
| | |
| | 1- PROPOSED SITE PLAN ON SHEET A-001: PROPOSED 6'-0" |
| | C.M.U. SITE WALL ON THE WEST SIDE WITH A WOOD GATE. |
| | SITE PLAN ALSO SHOWS A PROPOSED SWIMMING POOL. IT LOOKS |
| | LIKE THE PROPOSED SITE WALL IS GOING TO BE PART OF THE |
| | RESIDENTIAL SWIMMING BARRIER REQUIREMENTS OF SEC. |
| | R4501.17 FBC-RESIDENTIAL. IF THIS IS THE CASE, THEN |
| | PROVIDE DETAILS/SPECIFICATIONS FOR THIS ACCESS GATE |
| | SHOWING COMPLIANCE WITH SEC. R4501.17.1.8 |
| | FBC-RESIDENTIAL. IF THE SITE WALL IS NOT GOING TO BE |
| | PART OF THE SWIMMING BARRIER REQUIREMENTS, THEN CLEARLY |
| | STATE ON PLANS. |
| | NOTE: THIS PERMIT IS FOR THE SITE WALL CONSTRUCTION |
| | ONLY. |
| | |
| | RESPONSE: |
| | A)PROPOSED GATES SHALL HAVE NO MORE THAN 2 INCHES |
| | VERTICAL DISTANCE BETWEEN GRADE AND BOTTOM OF GATE. |
| | SEC. R4501.17.1.8 FBC-RESIDENTIAL AND SEC. R4501.17.1.1 |
| | FBC-RESIDENTIAL. |
| | |
| | B)PROVIDE COMPLETE DETAILS SPECIFICATIONS FOR POST |
| | SUPPORTING THE WOOD GATE ON THE PROPOSED CHAIN LINK |
| | FENCE. SPECIFY PROPOSED FOOTING. |
| | SEC. R301.2.1 FBC-RESIDENTIAL |
| | |
| | NOTE: THIS PERMIT IS FOR THE SITE WALL CONSTRUCTION |
| | ONLY. NEED SEPARATE FENCE POOL PERMIT. |
| | |
| | 2- DIGITAL SIGNATURE REVIEW: |
| | A)UNABLE TO VERIFY ARCHITECT'S DIGITAL SIGNATURE. |
| | PLEASE RESUBMIT WITH ARCHITECT'S VERIFIABLE DIGITAL |
| | SIGNATURE. |
| | |
| | ARCHITECTS |
| | 61G1-16.005 PROCEDURES FOR DIGITALLY SIGNING AND |
| | SEALING AND FOR ELECTRONICALLY TRANSMITTING PLANS, |
| | SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS. |
| | |
| | B)ENGINEER'S DIGITAL SIGNATURE DOESN'T COMPLY WITH THE |
| | REQUIREMENTS OF FBPE. NEED A SEPARATE TEXT BOX WITH THE |
| | TEXT BOX LANGUAGE IDENTICAL TO THE SAMPLES SHOWN BY |
| | FBPE. |
| | SEE FBPE.ORG/LEGAL/SIGNING-AND-SEALING-ENGINEERING-DOCU |
| | MENTS/ AND REVISE DIGITAL SIGNATURE AS REQUIRED. |
| | |
| | ENGINEERS |
| | SEC. 61G15-23.004 F.A.C. . PROCEDURES FOR DIGITALLY |
| | SIGNING AND SEALING ELECTRONICALLY TRANSMITTED PLANS, |
| | SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS. |
| | |
| | WHEN RESUBMITTING, A TRANSMITTAL LETTER LISTING THE |
| | ORIGINAL REVIEW COMMENT WITH A DESCRIPTION OF WHERE AND |
| | HOW THE COMMENT WAS ADDRESSED WILL HELP TO EXPEDITE THE |
| | REVIEW PROCESS. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |
| | PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY |
| | QUESTIONS REGARDING THESE COMMENTS, |
| | JULIO GOMEZ |
| | COMMERCIAL COMBINATION PLANS EXAMINER |
| | DEVELOPMENT SERVICES DEPARTMENT |
| | BUILDING DIVISION |
| | (561)805-6712 |
| | [email protected] |
| | |
| | |
| | 06/07/23 TALKED TO JENNY ALVAREZ (CURY ENTERPRISES). |
| | THEY ARE DOING THE SITE WALL ONLY. POOL CONTRACTOR OR |
| | OWNER IS DOING THE CHAIN LINK FENCE UNDER A SEPARATE |
| | PERMIT FOR THE OTHER PART OF THE CHILD BARRIER FENCE. |
| | JG. |