| 2023-03-20 07:41:32 | 1ST REVIEW FBC-2020 RES. GAS |
| | PERMIT- 23021260 |
| | 3/20/23 |
| | |
| | CODES IN EFFECT: |
| | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION |
| | 2020 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) SHEET 3: THE PLAN SHOWS A GAS COOKTOP AND A GAS |
| | FIRED TANKLESS WATER HEATER. PLEASE PROVIDE A COMPLETE |
| | GAS RISER DRAWING IN COMPLIANCE WITH SEC. 107.3.5.3 |
| | WPB. THE RISER SHALL SHOW PROVIDE THE FOLLOWING |
| | INFORMATION- |
| | A) TYPE OF GAS- NATURAL OR LP. |
| | B) DELIVERY PRESSURE AT THE METER. |
| | C) TOTAL BTU LOAD AND INDIVIDUAL APPLIANCE BTU LOADS. |
| | D) TYPES AND SIZES OF PIPING. |
| | E) TOTAL DEVELOPED LENGTH OF THE SYSTEM FROM THE METER |
| | TO THE MOST REMOTE APPLIANCE OUTLET. |
| | F) BRANCH AND CUT PIPE LENGTH MEASUREMENTS. |
| | G) LOCATIONS OF REGULATORS, SHUTOFF VALVES. |
| | H) OUTLET PRESSURES AT REGULATORS. |
| | I) LOCATIONS AND TYPES OF PIPE SLEEVES. |
| | J) PIPE SIZING TABLES. |
| | |
| | 2) SHEET 3: PROVIDE COMBUSTION AIR CALCULATIONS FOR THE |
| | NEW COOK TOP- SEC. G2407.1 FBC RES. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |