| 2023-06-12 11:20:54 | 2ND REVIEW FBC-2020 RES. GAS |
| | PERMIT- 23021253 |
| | 6/12/23 |
| | |
| | CODES IN EFFECT: |
| | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION |
| | 2020 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. THE CORRECTED RISER |
| | DRAWING WAS NOT UPLOADED FOR REVEW. THE 1ST REVIEW |
| | COMMENTS BELOW STILL EXIST. |
| | |
| | 1) GAS RISER: PROVIDE A COMPLETE RISER DRAWING THAT |
| | INCLUDES THE NEW GAS PIPING TO THE GENERATOR AND |
| | EXISTING GAS PIPING AND APPLIANCES AT THE RESIDENCE- |
| | SECTION G2412.3 & G2412.4 FBC RES. WPB BUILDING DEPT. |
| | RECORDS INDICATE PREVIOUS GAS PIPING PERMIT FOR WATER |
| | HEATER AND DRYER- 07020505. PLEASE REVISE THE RISER |
| | DRAWING PER ITEMS A- C BELOW. |
| | |
| | A) SHOW THE TOTAL BTU LOAD OF THE SYSTEM AND INDIVIDUAL |
| | APPLIANCE BTU LOADS. |
| | |
| | B) SHOW THE SIZE OF THE MAIN SUPPLY PIPE AT THE METER |
| | AND THE SIZE OF THE SUPPLY PIPE AT THE GENERATOR. |
| | |
| | C) AT THE MAIN SUPPLY PIPE PLEASE SHOW BOTH THE NEW |
| | BRANCH PIPING POINT OF CONNECTION AND THE EXISTING |
| | BRANCH PIPING POINT OF CONNECTION. IDENTIFY THE TYPE |
| | AND SIZE OF THE EXISTING BRANCH PIPING. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |