| 2023-03-16 16:01:19 | 1ST REVIEW FBC-2020 RES. GAS | | | PERMIT- 23021253 | | | 3/16/23 | | | | | | CODES IN EFFECT: | | | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION | | | 2020 | | | FS- FLORIDA STATUTES | | | FAC- FLORIDA ADMINISTRATIVE CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) GAS RISER: PROVIDE A COMPLETE RISER DRAWING THAT | | | INCLUDES THE NEW GAS PIPING TO THE GENERATOR AND | | | EXISTING GAS PIPING AND APPLIANCES AT THE RESIDENCE- | | | SECTION G2412.3 & G2412.4 FBC RES. WPB BUILDING DEPT. | | | RECORDS INDICATE PREVIOUS GAS PIPING PERMIT FOR WATER | | | HEATER AND DRYER- 07020505. PLEASE REVISE THE RISER | | | DRAWING PER ITEMS A- C BELOW. | | | | | | A) SHOW THE TOTAL BTU LOAD OF THE SYSTEM AND INDIVIDUAL | | | APPLIANCE BTU LOADS. | | | | | | B) SHOW THE SIZE OF THE MAIN SUPPLY PIPE AT THE METER | | | AND THE SIZE OF THE SUPPLY PIPE AT THE GENERATOR. | | | | | | C) AT THE MAIN SUPPLY PIPE PLEASE SHOW BOTH THE NEW | | | BRANCH PIPING POINT OF CONNECTION AND THE EXISTING | | | BRANCH PIPING POINT OF CONNECTION. IDENTIFY THE TYPE | | | AND SIZE OF THE EXISTING BRANCH PIPING. | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL/PLUMBING PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | | | | | | | | | | |
|