| Plan Review Notes For Permit 23021250 |
| Permit Number |
23021250 |
|
| Review Stop |
B |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2023-03-17 09:19:46 | PETER E VALENTI | | | BUILDING PLANS EXAMINER II/INSPECTOR | | | [email protected] | | | 561 805 6673 | | | | | | FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020) | | | FBC B = FBC BUILDING | | | FBC R = FBC RESIDENTIAL | | | FBC EB = FBC EXISTING BUILDING | | | FBC A = FBC ACCESSIBILITY | | | FBC EC = FBC ENERGY CONSERVATION | | | FBC M = FBC MECHANICAL | | | FBC FG = FBC FUEL | | | | | | BUILDING REVIEW DENIED: | | | | | | FBC B 107.2.1, THE SCHEDULE SHOWS THE 5/16" ULTRACON & | | | TAPCON ANCHOR SPACING AT 18" ON CENTER, WHERE AS THE | | | PRODUCT APPROVAL SHEET 7 OF 14, TABLE A2, | | | INDICATES(CIRCLED) 8" ON CENTER ANCHOR SPACING. PLEASE | | | CORRECT THE SCHEDULE TO MATCH THE PRODUCT APPROVAL. |
|