| 2023-04-28 11:01:00 | 2ND REVIEW FBC-2020 RES. GAS |
| | PERMIT- 23021238 |
| | 4/28/23 |
| | |
| | CODES IN EFFECT: |
| | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION |
| | 2020 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) SHEET P701 REVISED GAS RISER COMMENTS- SEC. |
| | 107.3.5.3 FBC RES. |
| | |
| | A) BASED ON TABLE G2413.4(1) FBC RES THE 1-INCH STEEL |
| | PIPE SUPPLYING GWH 1 & 2 SHALL BE INCREASED TO |
| | 1-1/4-INCH, AND THE 3/4-INCH LINE TO GWH-2 SHALL BE |
| | INCREASED TO 1-INCH. |
| | |
| | B) SHOW THE GAS PIPING BRANCH LINE TO THE DRYERS AND |
| | LOCATIONS OF REGULATORS. |
| | |
| | C) PLEASE SHOW A LOW-PRESSURE REGULATOR AT THE BBQ AND |
| | SIZE AND LENGTH OF THE SUPPLY PIPE. |
| | |
| | 2) P101A & P701: SHOW THE LOCATION AND SIZE OF THE |
| | COMBUSTION AIR INTAKE LOUVER FOR THE GENERATOR- SEC. |
| | G2407.6.2. PLEASE NOTE IF USING THE ONE-OPENING METHOD |
| | THE MINIMUM NET OPENING SIZE OF THE LOUVER SHALL BE 625 |
| | SQ. INCHES AND THE LOUVER SHALL COMMENCE WITHIN |
| | 12-INCHES OF THE TOP OF THE ENCLOSURE. |
| | |
| | 3) P101A & P701: 2ND REQUEST FOR GENERATOR EXHAUST |
| | VENTING PLAN- SEC. G2427.1. |
| | |
| | 4) P101A, P102 & P701: 2ND REQUEST FOR COMBUSTION AIR |
| | AND VENTING PLANS FOR GWH-1 & 2. THE REVISED PLAN |
| | INDICATES A DIRECT, CONCENTRIC TYPE SYSTEM THROUGH THE |
| | ROOF. PLEASE PROVIDE A DIAGRAM SHOWING THE TYPE AND |
| | SIZE OF CONCENTRIC VENT, VENT RUN, AND TERMINATION |
| | LOCATIONS ON THE ROOF- SEC. G2427.2 & G2427.8 ITEM 3. |
| | |
| | 5) P101A & P701: THE REVISED PLAN SHOWS COMBUSTION AIR |
| | FOR THE DRYERS WILL BE SUPPLIED MECHANICALLY. PLEASE |
| | REFER TO SEC. G2407.9 AND SHOW HOW THE AIR WILL BE |
| | PROVIDED MECHANICALLY AT A RATE OF 0.35 CFM PER 1000 |
| | BTUH. PLEASE NOTE IF USING THE AC SYSTEM, THE SYSTEM |
| | SHALL PROVIDE THE SPECIFIED AIR RATE IN ADDITION TO THE |
| | REQUIRED VENTILATION AIR. ADVISORY- PLEASE REVIEW SEC. |
| | G2407.1 EXCEPTION FOR MAKEUP AIR USE PER G2439.5. |
| | |
| | 6) P101A & P701: THE REVISED PLAN SHOWS COMBUSTION AIR |
| | FOR THE RANGE TO BE PROVIDED VIA A CONCENTRIC VENT AIR |
| | INTAKE VIA THE ROOF. PLEASE REFER TO G2407.11 AND |
| | PROVIDE DETAILS INCLUDING TYPE AND SIZE OF COMBUSTION |
| | AIR DUCT, DUCT RUN AND TERMINATION LOCATION. IF |
| | COMBINING INDOOR AND OUTDOOR AIR PLEASE SEE SECS. |
| | G2407.7- G2407.7.3 AND PROVIDE CALCULATIONS AND |
| | DETAILS. |
| | |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |