Plan Review Notes
Plan Review Notes For Permit 23021238
Permit Number 23021238
Review Stop G
Sequence Number 2
Notes
Date Text
2023-04-28 11:01:002ND REVIEW FBC-2020 RES. GAS
 PERMIT- 23021238
 4/28/23
  
 CODES IN EFFECT:
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION
 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET P701 REVISED GAS RISER COMMENTS- SEC.
 107.3.5.3 FBC RES.
  
 A) BASED ON TABLE G2413.4(1) FBC RES THE 1-INCH STEEL
 PIPE SUPPLYING GWH 1 & 2 SHALL BE INCREASED TO
 1-1/4-INCH, AND THE 3/4-INCH LINE TO GWH-2 SHALL BE
 INCREASED TO 1-INCH.
  
 B) SHOW THE GAS PIPING BRANCH LINE TO THE DRYERS AND
 LOCATIONS OF REGULATORS.
  
 C) PLEASE SHOW A LOW-PRESSURE REGULATOR AT THE BBQ AND
 SIZE AND LENGTH OF THE SUPPLY PIPE.
  
 2) P101A & P701: SHOW THE LOCATION AND SIZE OF THE
 COMBUSTION AIR INTAKE LOUVER FOR THE GENERATOR- SEC.
 G2407.6.2. PLEASE NOTE IF USING THE ONE-OPENING METHOD
 THE MINIMUM NET OPENING SIZE OF THE LOUVER SHALL BE 625
 SQ. INCHES AND THE LOUVER SHALL COMMENCE WITHIN
 12-INCHES OF THE TOP OF THE ENCLOSURE.
  
 3) P101A & P701: 2ND REQUEST FOR GENERATOR EXHAUST
 VENTING PLAN- SEC. G2427.1.
  
 4) P101A, P102 & P701: 2ND REQUEST FOR COMBUSTION AIR
 AND VENTING PLANS FOR GWH-1 & 2. THE REVISED PLAN
 INDICATES A DIRECT, CONCENTRIC TYPE SYSTEM THROUGH THE
 ROOF. PLEASE PROVIDE A DIAGRAM SHOWING THE TYPE AND
 SIZE OF CONCENTRIC VENT, VENT RUN, AND TERMINATION
 LOCATIONS ON THE ROOF- SEC. G2427.2 & G2427.8 ITEM 3.
  
 5) P101A & P701: THE REVISED PLAN SHOWS COMBUSTION AIR
 FOR THE DRYERS WILL BE SUPPLIED MECHANICALLY. PLEASE
 REFER TO SEC. G2407.9 AND SHOW HOW THE AIR WILL BE
 PROVIDED MECHANICALLY AT A RATE OF 0.35 CFM PER 1000
 BTUH. PLEASE NOTE IF USING THE AC SYSTEM, THE SYSTEM
 SHALL PROVIDE THE SPECIFIED AIR RATE IN ADDITION TO THE
 REQUIRED VENTILATION AIR. ADVISORY- PLEASE REVIEW SEC.
 G2407.1 EXCEPTION FOR MAKEUP AIR USE PER G2439.5.
  
 6) P101A & P701: THE REVISED PLAN SHOWS COMBUSTION AIR
 FOR THE RANGE TO BE PROVIDED VIA A CONCENTRIC VENT AIR
 INTAKE VIA THE ROOF. PLEASE REFER TO G2407.11 AND
 PROVIDE DETAILS INCLUDING TYPE AND SIZE OF COMBUSTION
 AIR DUCT, DUCT RUN AND TERMINATION LOCATION. IF
 COMBINING INDOOR AND OUTDOOR AIR PLEASE SEE SECS.
 G2407.7- G2407.7.3 AND PROVIDE CALCULATIONS AND
 DETAILS.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  