| 2023-03-06 07:33:37 | 1ST REVIEW FMC |
| | PERMIT: 23021238 |
| | |
| | CODES IN EFFECT: 2020 |
| | |
| | FBC- FLORIDA BUILDING CODE |
| | FMC- FLORIDA MECHANICAL CODE |
| | FEC- FLORIDA ENERGY CONSERVATION |
| | FGC- FLORIDA FUEL GAS |
| | FEX- FLORIDA EXISTING BUILDING CODE |
| | FRC- FLORIDA RESIDENTIAL BUILDING CODE |
| | F.S.- FLORIDA STATUTES |
| | FAC- FLORIDA ACCESSIBILITY CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) THE ENERGY CALCULATIONS WILL NEED THE PREPARERS NAME |
| | AND SIGNED BY THE OWNER/AGENT. |
| | |
| | 2) ADD A NOTE ON THE MECHANICAL DRAWINGS THAT THE |
| | GENERATOR WILL REQUIRE A SEPARATE PERMIT APPLICATION, |
| | DOCUMENT SUBMITTAL AND PLAN REVIEW AS THE GENERATOR |
| | WILL NOT BE REVIEWED UNDER THIS PERMIT. |
| | |
| | 3) THE MECHANICAL CALCULATIONS ARE NOT CONSISTENT WITH |
| | THE MECHANICAL DRAWINGS SUBMITTED. THE EQUIPMENT SIZING |
| | CALCULATIONS SHOW 3 SYSTEMS. SHEET M600 HAS 18 AHU???S |
| | AND 12 HEAT PUMPS. SHEETS M101A AND M101B SHOW ONLY 10 |
| | HEAT PUMPS. |
| | |
| | 4) THE WATER CLOSET COMPARTMENT IN THE PRIMARY BATH ON |
| | THE 2ND FLOOR WILL NEED TO MEET THE EXHAUST REQUIREMENT |
| | OF FRC R303.3 |
| | |
| | 5) SHEET M101A: IDENTIFY THE ITEM THAT IS LEAVING THE |
| | GENERATOR TOWARDS THE L-1 HP-1. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM. |
| | |