2023-03-06 07:33:371ST REVIEW FMC
 PERMIT: 23021238
  
 CODES IN EFFECT: 2020
  
 FBC- FLORIDA BUILDING CODE
 FMC- FLORIDA MECHANICAL CODE
 FEC- FLORIDA ENERGY CONSERVATION
 FGC- FLORIDA FUEL GAS
 FEX- FLORIDA EXISTING BUILDING CODE
 FRC- FLORIDA RESIDENTIAL BUILDING CODE
 F.S.- FLORIDA STATUTES
 FAC- FLORIDA ACCESSIBILITY CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THE ENERGY CALCULATIONS WILL NEED THE PREPARERS NAME
 AND SIGNED BY THE OWNER/AGENT.
  
 2) ADD A NOTE ON THE MECHANICAL DRAWINGS THAT THE
 GENERATOR WILL REQUIRE A SEPARATE PERMIT APPLICATION,
 DOCUMENT SUBMITTAL AND PLAN REVIEW AS THE GENERATOR
 WILL NOT BE REVIEWED UNDER THIS PERMIT.
  
 3) THE MECHANICAL CALCULATIONS ARE NOT CONSISTENT WITH
 THE MECHANICAL DRAWINGS SUBMITTED. THE EQUIPMENT SIZING
 CALCULATIONS SHOW 3 SYSTEMS. SHEET M600 HAS 18 AHU???S
 AND 12 HEAT PUMPS. SHEETS M101A AND M101B SHOW ONLY 10
 HEAT PUMPS.
  
 4) THE WATER CLOSET COMPARTMENT IN THE PRIMARY BATH ON
 THE 2ND FLOOR WILL NEED TO MEET THE EXHAUST REQUIREMENT
 OF FRC R303.3
  
 5) SHEET M101A: IDENTIFY THE ITEM THAT IS LEAVING THE
 GENERATOR TOWARDS THE L-1 HP-1.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  