| Plan Review Notes For Permit 23021238 |
| Permit Number |
23021238 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2023-03-15 14:48:45 | FLORIDA BUILDING CODE 2020 7TH EDITION | | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED | | | NFPA 70 2017 EDITION | | | | | | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW | | | | | | 1. LOAD CALCULATION FOR SERVICE DOES NOT INCLUDE | | | EXISTING EQUIPMENT AS LISTED ON THE MOTOR CIRCUIT | | | SCHEDULE ON PAGE 133 E600-ELECTRICAL SCHEDULE (THE | | | CALCULATION ONLY SHOWS 12 AHU). | | | NEC 220 | | | | | | 2. SERVICE RECEPTACLE PER NEC 210.63 OR IRC E3901.11 | | | THE RECEPTACLE MUST BE IN A READILY ACCESSIBLE LOCATION | | | FROM THE EQUIPMENT AND MUST BE GFCI-PROTECTED AS | | | APPLICABLE TO OUTDOOR RECEPTACLES AT DWELLING | | | OCCUPANCIES. | | | | | | END OF COMMENTS | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM. | | | | | | RUBEN PEREZ PERDOMO, P.E. | | | ELECTRICAL PLANS EXAMINER | | | 561-805-6738 | | | [email protected] | | | |
|