Plan Review Notes
Plan Review Notes For Permit 23021237
Permit Number 23021237
Review Stop P
Sequence Number 2
Notes
Date Text
2023-04-24 11:19:532ND PLUMBING REVIEW
  
 THIS PLAN WAS REVIEWED FOR CODE COMPLIANCE AND FAILED
 BY RYAN BROWN WITH THE FOLLOWING COMMENTS.
  
  
 1. IF THERE ARE TWO METERS, ONE FOR IRRIGATION AND ONE
 FOR DOMESTIC WATER, EACH WILL NEED ITS OWN BACKFLOW AND
 ASSOCIATED PERMIT. ONLY ONE BACKFLOW PERMIT HAS BEEN
 APPLIED FOR.
  
 2017 WPB AMEND - 105.1/107.3 -- PAGE C4.0 INDICATES TWO
 SEPARATE METER CONNECTIONS. ONE FOR IRRIGATION AND ONE
 FOR THE POTABLE WATER. EACH WILL REQUIRE ITS OWN
 BACKFLOW PERMIT. THESE ARE REQUIRED TO BE APPLIED FOR
 PRIOR TO ISSUANCE OF THE PRIMARY PERMIT. YOU CAN SUBMIT
 AN APPLICATION "TBD" (TO BE DETERMINED) IF YOU DO NOT
 HAVE A CONTRACTOR SELECTED BY EMAILING A COMPLETED
 PERMIT APPLICATION TO [email protected]. AFTER
 YOU HAVE THE PERMIT(S) GENERATED, NOTIFY ME VIA EMAIL
 OR NOTE IN THE RESPONSE LETTER AND I WILL COMPLY THIS
 COMMENT.
  
 2. NOT ADDRESSED --
  
 2017 WPB AMEND - 105.1/107.3 -- IRRIGATION WILL REQUIRE
 A SEPARATE PERMIT
  
 3. DONE - RISER SHOWN - SEE BELOW FOR INDIVIDUAL
 COMMENTS NOT ADDRESSED --
  
 A) DONE
  
 B) DONE
  
 C) DONE
  
 D) DONE
  
 E) DONE
  
 F) PAGE 201A PRIMARY BATH - 2017 WPB AMEND 107.3.5.3
 (12) - THE FLOOR PLAN SHOWS A 2" SAN UP TO SECOND FLOOR
 WHICH GOES TO THE WATER CLOSET. THE ISOMETRIC SHOWS A
 3". FIX THE FLOOR PLAN TO SHOW THE REQUIRED 3" TO THE
 WATER CLOSET.
  
 G) WYE IS STILL FACING BACKWARDS --
 PAGE 201A PRIMARY BATH - 2017 WPB AMEND 107.3.5.3 (12)
 - IN THE SAME AREA IT APPEARS ONE OF THE WYES IS FACING
 BACKWARDS.
  
 H) PAGE 201A PRIMARY BATH - THE BATHTUB IS MISSING FROM
 THE ISOMETRIC AND THE FLOOR PLAN.
  
 I) NEW COMMENT - THE ISOMETRIC DOES NOT MATCH THE FLOOR
 PLAN. THE TWO BATHROOMS NEAREST THE IT ROOM ARE NOT
 SHOWN THE SAME ON THE FLOOR PLAN AS THEY ARE ON THE
 ISOMETRIC. THE SHOWER AND WATER CLOSETS IN BOTH
 BATHROOMS ARE SWITCHED AROUND.
  
 4. IT IS TYPICAL AND MOST HELPFUL IF YOU SHOW A SECOND
 FLOOR PLUMBING PLAN WITH THE SANITARY TO THE SECOND
 FLOOR PLUMBING FIXTURES IMPOSED UNDER THE 2ND FLOOR UP
 TO THE CORRESPONDING 2ND FLOOR FIXTURES, MUCH LIKE THE
 1ST FLOOR IS SHOWN.
 2017 WPB AMEND 107.3.5.3 (12) - THE SECOND-FLOOR
 PLUMBING PLAN APPEARS TO BE MISSING.
  
 5. DONE
  
 6. 2017 WPB AMENDS 107.2.1 - THE REFERENCED PAGES IN
 THE KEY NOTES WITHIN THE PLAN ARE MISSING - A727, A718,
 A731, A734, ETC..?
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
  
 RYAN W. BROWN
 CHIEF PLUMBING INSPECTOR
 OFFICE: 561-805-6692
 CELL: 561-517-4293
 EMAIL: [email protected]
  
  
 V7 FPC - 2020 FLORIDA PLUMBING CODE
 V7 FGC - 2020 FLORIDA FUEL GAS
 V7 FRC - 2020 FLORIDA RESIDENTIAL BUILDING CODE
 V7 FAC - 2020 FLORIDA ACCESSIBILITY CODE
 V7 FEX - 2020 FLORIDA EXISTING BUILDING CODE
 V7 FEC - 2020 FLORIDA ENERGY CONSERVATION
 2021 F.S. - 2021 FLORIDA STATUTES
 2021 F.A.C. - 2021 FLORIDA ADMINISTRATIVE CODE
 2017 WPB AMEND - 2017 WEST PALM BEACH AMENDMENTS TO THE
 FBC CHAPTER 1
  
  