| Date |
Text |
| 2023-04-24 11:19:53 | 2ND PLUMBING REVIEW |
| | |
| | THIS PLAN WAS REVIEWED FOR CODE COMPLIANCE AND FAILED |
| | BY RYAN BROWN WITH THE FOLLOWING COMMENTS. |
| | |
| | |
| | 1. IF THERE ARE TWO METERS, ONE FOR IRRIGATION AND ONE |
| | FOR DOMESTIC WATER, EACH WILL NEED ITS OWN BACKFLOW AND |
| | ASSOCIATED PERMIT. ONLY ONE BACKFLOW PERMIT HAS BEEN |
| | APPLIED FOR. |
| | |
| | 2017 WPB AMEND - 105.1/107.3 -- PAGE C4.0 INDICATES TWO |
| | SEPARATE METER CONNECTIONS. ONE FOR IRRIGATION AND ONE |
| | FOR THE POTABLE WATER. EACH WILL REQUIRE ITS OWN |
| | BACKFLOW PERMIT. THESE ARE REQUIRED TO BE APPLIED FOR |
| | PRIOR TO ISSUANCE OF THE PRIMARY PERMIT. YOU CAN SUBMIT |
| | AN APPLICATION "TBD" (TO BE DETERMINED) IF YOU DO NOT |
| | HAVE A CONTRACTOR SELECTED BY EMAILING A COMPLETED |
| | PERMIT APPLICATION TO [email protected]. AFTER |
| | YOU HAVE THE PERMIT(S) GENERATED, NOTIFY ME VIA EMAIL |
| | OR NOTE IN THE RESPONSE LETTER AND I WILL COMPLY THIS |
| | COMMENT. |
| | |
| | 2. NOT ADDRESSED -- |
| | |
| | 2017 WPB AMEND - 105.1/107.3 -- IRRIGATION WILL REQUIRE |
| | A SEPARATE PERMIT |
| | |
| | 3. DONE - RISER SHOWN - SEE BELOW FOR INDIVIDUAL |
| | COMMENTS NOT ADDRESSED -- |
| | |
| | A) DONE |
| | |
| | B) DONE |
| | |
| | C) DONE |
| | |
| | D) DONE |
| | |
| | E) DONE |
| | |
| | F) PAGE 201A PRIMARY BATH - 2017 WPB AMEND 107.3.5.3 |
| | (12) - THE FLOOR PLAN SHOWS A 2" SAN UP TO SECOND FLOOR |
| | WHICH GOES TO THE WATER CLOSET. THE ISOMETRIC SHOWS A |
| | 3". FIX THE FLOOR PLAN TO SHOW THE REQUIRED 3" TO THE |
| | WATER CLOSET. |
| | |
| | G) WYE IS STILL FACING BACKWARDS -- |
| | PAGE 201A PRIMARY BATH - 2017 WPB AMEND 107.3.5.3 (12) |
| | - IN THE SAME AREA IT APPEARS ONE OF THE WYES IS FACING |
| | BACKWARDS. |
| | |
| | H) PAGE 201A PRIMARY BATH - THE BATHTUB IS MISSING FROM |
| | THE ISOMETRIC AND THE FLOOR PLAN. |
| | |
| | I) NEW COMMENT - THE ISOMETRIC DOES NOT MATCH THE FLOOR |
| | PLAN. THE TWO BATHROOMS NEAREST THE IT ROOM ARE NOT |
| | SHOWN THE SAME ON THE FLOOR PLAN AS THEY ARE ON THE |
| | ISOMETRIC. THE SHOWER AND WATER CLOSETS IN BOTH |
| | BATHROOMS ARE SWITCHED AROUND. |
| | |
| | 4. IT IS TYPICAL AND MOST HELPFUL IF YOU SHOW A SECOND |
| | FLOOR PLUMBING PLAN WITH THE SANITARY TO THE SECOND |
| | FLOOR PLUMBING FIXTURES IMPOSED UNDER THE 2ND FLOOR UP |
| | TO THE CORRESPONDING 2ND FLOOR FIXTURES, MUCH LIKE THE |
| | 1ST FLOOR IS SHOWN. |
| | 2017 WPB AMEND 107.3.5.3 (12) - THE SECOND-FLOOR |
| | PLUMBING PLAN APPEARS TO BE MISSING. |
| | |
| | 5. DONE |
| | |
| | 6. 2017 WPB AMENDS 107.2.1 - THE REFERENCED PAGES IN |
| | THE KEY NOTES WITHIN THE PLAN ARE MISSING - A727, A718, |
| | A731, A734, ETC..? |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM. |
| | |
| | |
| | RYAN W. BROWN |
| | CHIEF PLUMBING INSPECTOR |
| | OFFICE: 561-805-6692 |
| | CELL: 561-517-4293 |
| | EMAIL: [email protected] |
| | |
| | |
| | V7 FPC - 2020 FLORIDA PLUMBING CODE |
| | V7 FGC - 2020 FLORIDA FUEL GAS |
| | V7 FRC - 2020 FLORIDA RESIDENTIAL BUILDING CODE |
| | V7 FAC - 2020 FLORIDA ACCESSIBILITY CODE |
| | V7 FEX - 2020 FLORIDA EXISTING BUILDING CODE |
| | V7 FEC - 2020 FLORIDA ENERGY CONSERVATION |
| | 2021 F.S. - 2021 FLORIDA STATUTES |
| | 2021 F.A.C. - 2021 FLORIDA ADMINISTRATIVE CODE |
| | 2017 WPB AMEND - 2017 WEST PALM BEACH AMENDMENTS TO THE |
| | FBC CHAPTER 1 |
| | |
| | |