| 2023-05-16 16:23:49 | PEER REVIEW COMPLETED RMCP |
| 2023-05-16 14:36:40 | 2ND NFIP REVIEW |
| | RESULTS: CORRECTIONS NEEDED |
| | |
| | CHRISTOPHER S. THROOP, CBO, BN, PX, CFM |
| | PLANS EXAMINER II |
| | CITY OF WEST PALM BEACH |
| | (561) 805-6726 |
| | [email protected] |
| | |
| | CODES IN EFFECT: |
| | 2020 FLORIDA BUILDING CODE, 7TH EDITION W/2017 WEST |
| | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, |
| | CHAPTER 1 ADMINISTRATION |
| | CITY ORDINANCE NO. 4658-16 AND NO. 4729-17 |
| | FEMA DESK REFERENCE P 758 |
| | FBC R322 FLOOD-RESISTANT CONSTRUCTION |
| | |
| | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT |
| | |
| | 1.THIS PROJECT IS LOCATED IN A SPECIAL FLOOD HAZARD |
| | AREA (SFHA). THE FLOOD ZONE DESIGNATIONS FOR THIS SITE |
| | ARE AE 6 AND AE 7 WITH A BASE FLOOD ELEVATIONS (BFE) OF |
| | 6'0" AND 7'0" NAVD. |
| | THE CITY OF WEST PALM BEACH (THROUGH ORDINANCE NO. |
| | 4729-17) REQUIRES AN ADDITIONAL 24 INCHES OF FREEBOARD. |
| | THE DESIGN FLOOD ELEVATION (DFE) SHALL BE AT OR ABOVE |
| | 9'0" NAVD. |
| | |
| | NOTICE: 1ST REVIEW OF THE CONSTRUCTION DRAWING EC: |
| | |
| | 1. LINES A8B) & C) SHALL BE N/A. (PER EC INSTRUCTIONS) |
| | |
| | 2. LINES 9AB) & C) SHALL BE N/A. (PER EC INSTRUCTIONS) |
| | |
| | 3. LINE C2E) STATES MACHINERY SERVICING BUILDING |
| | (GENERATOR PER COMMENTS) WILL BE AT 10.5'. PLAN PAGE |
| | A201B SHOWS MECH. ROOM (GENERATOR) IS AT 10.0'. PLEASE |
| | CLARIFY? |
| | |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| 2023-05-16 10:20:16 | PEER REVIEW REQUESTED 5/16/23. CT |