Date Text
2023-05-02 11:14:322ND REVIEW FMC
 PERMIT: 23021237
  
 CODES IN EFFECT: 2020
  
 FBC- FLORIDA BUILDING CODE
 FMC- FLORIDA MECHANICAL CODE
 FEC- FLORIDA ENERGY CONSERVATION
 FGC- FLORIDA FUEL GAS
 FEX- FLORIDA EXISTING BUILDING CODE
 FRC- FLORIDA RESIDENTIAL BUILDING CODE
 F.S.- FLORIDA STATUTES
 FAC- FLORIDA ACCESSIBILITY CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THE MECHANICAL EQUIPMENT SIZING CALCULATIONS WERE
 NOT SUBMITTED IN THIS REVIEW CYCLE. PROVIDE THE
 CORRECTED MECHANICAL EQUIPMENT SIZING CALCULATIONS.
  
 2) PROVIDE THE CALCULATIONS FOR THE INTAKE LOUVERS
 SIZING AND THE EXHAUST FOR THE GENERATOR ROOM.
 FBC107.3.5
  
 3) THE ENGINEER OF RECORD WILL NEED TO DIGITALLY SIGN
 THE SUBMITTED MECHANICAL DRAWINGS. FS 471/481
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  