Plan Review Notes
Plan Review Notes For Permit 23021237
Permit Number 23021237
Review Stop P
Sequence Number 1
Notes
Date Text
2023-02-28 14:03:141ST PLUMBING REVIEW
  
 THIS PLAN WAS REVIEWED FOR CODE COMPLIANCE AND FAILED
 BY RYAN BROWN WITH THE FOLLOWING COMMENTS.
  
 NOTE: PAGE SP100-SITE PLAN - THIS LAYOUT DOES NOT MATCH
 THE REST OF THE PAGES.
  
 1. 2017 WPB AMEND - 105.1/107.3 -- PAGE C4.0 INDICATES
 TWO SEPARATE METER CONNECTIONS. ONE FOR IRRIGATION AND
 ONE FOR THE POTABLE WATER. EACH WILL REQUIRED ITS OWN
 BACKFLOW PERMIT. THESE ARE REQUIRED TO BE APPLIED FOR
 PRIOR TO ISSUANCE OF THE PRIMARY PERMIT. YOU CAN SUBMIT
 AN APPLICATION "TBD" (TO BE DETERMINED) IF YOU DO NOT
 HAVE A CONTRACTOR SELECTED BY EMAILING A COMPLETED
 PERMIT APPLICATION TO [email protected]. AFTER
 YOU HAVE THE PERMIT(S) GENERATED, NOTIFY ME VIA EMAIL
 OR NOTE IN THE RESPONSE LETTER AND I WILL COMPLY THIS
 COMMENT.
  
 2. 2017 WPB AMEND - 105.1/107.3 -- IRRIGATION WILL
 REQUIRE A SEPARATE PERMIT
  
 3. 2017 WPB AMEND 107.3.5.3 (12) - PLEASE ADD A RISER
 IN ISOMETRIC FORM FOR PLUMBING REVIEW. A RISER IS
 ALWAYS REQUIRED. A PRELIMINARY REVIEW OF THE SANITARY
 FOLLOWS BUT WILL NEED TO HAVE THE ISOMETRIC FOR FULL
 REVIEW:
 A) PAGE P200B - POOL BATH AREA - 2020 FRC P3108.1 - THE
 KITCHENETTE CANNOT CONNECT INTO THE SHOWER FIXTURE
 DRAIN. IF A WET VENT SYSTEM IS BEING USED IN THE
 BATHROOM AREA, ANY OTHER FIXTURES WOULD NEED TO
 DISCHARGE DOWNSTREAM OF THE BATHROOM GROUP.
 B) PAGE P200B - POOL BATH AREA - 2020 FRC P3108.2.1 -
 IT APPEARS, BUT IS UNCLEAR THAT THE WATER CLOSET AND
 SHOWER ARE BOTH UPSTREAM OF THE VENTED FIXTURE'S
 (LAVATORY) CONNECTION. ONLY ONE FIXTURE WOULD BE
 ALLOWED UPSTREAM OF THE VENTED FIXTURE THAT CREATES THE
 WET VENT FOR THAT BATHROOM GROUP.
 C) PAGE P200B - POOL BATH AREA - 2020 FPC P3104.4 - THE
 PRIVATE WATER CLOSET HAS A DRYVENT THAT IS HORIZONTAL
 BELOW THE FLOOD RIM OF THE FIXTURE. A VENT SHALL RISE
 VERTICALLY TO 6" ABOVE THE FLOOD RIM OF THE FIXURE(S)
 SERVED.
 D) PAGE P200A - STAFF LOUNGE AREA - THE WATER CLOSET IS
 NOT VENTED TO CODE.
 E) PAGE P200A - KITCHEN AREA - 2020 FRC P3101.2.1 - IT
 IS UNCLEAR IF THE KITCHEN TRAPS ARE VENTED/STUDOR
 VENTED?
 THIS IS ALL I CAN SEE FOR NOW. PLEASE SUBMIT THE SECOND
 FLOOR PLAN AS WELL AS THE COMPLETE ISOMETRIC FOR THE
 SANITARY FOR REVIEW. INCLUDE THE CONTINUATION OF THE
 VENTING IN THE SANITARY ISOMETRIC
 F) PAGE 201A - 2017 WPB AMEND 107.3.5.3 (12) - IT
 APPEARS THE UPSTAIRS WATER CLOSET AND BATHTUB ARE
 MISSING FROM THE DRAWING.
 G)PAGE 201A - 2017 WPB AMEND 107.3.5.3 (12) - IN THE
 SAME AREA IT APPEARS ONE OF THE WYES IS FACING
 BACKWARDS.
  
 4. 2017 WPB AMEND 107.3.5.3 (12) - THE SECOND FLOOR
 PLUMBING PLAN APPEARS TO BE MISSING.
  
 5. PAGE 701 - 2017 WPB AMEND 107.3.5.3 (12) - THERE IS
 A NOTE ON THE WATER RISR-EAST THAT STATES "REFER TO
 P702" AND THERE IS NO PAGE 702.
  
  
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
  
 RYAN W. BROWN
 CHIEF PLUMBING INSPECTOR
 OFFICE: 561-805-6692
 CELL: 561-517-4293
 EMAIL: [email protected]
  
  
 V7 FPC - 2020 FLORIDA PLUMBING CODE
 V7 FGC - 2020 FLORIDA FUEL GAS
 V7 FRC - 2020 FLORIDA RESIDENTIAL BUILDING CODE
 V7 FAC - 2020 FLORIDA ACCESSIBILITY CODE
 V7 FEX - 2020 FLORIDA EXISTING BUILDING CODE
 V7 FEC - 2020 FLORIDA ENERGY CONSERVATION
 2021 F.S. - 2021 FLORIDA STATUTES
 2021 F.A.C. - 2021 FLORIDA ADMINISTRATIVE CODE
 2017 WPB AMEND - 2017 WEST PALM BEACH AMENDMENTS TO THE
 FBC CHAPTER 1
  
  