| Date |
Text |
| 2023-02-28 14:03:14 | 1ST PLUMBING REVIEW |
| | |
| | THIS PLAN WAS REVIEWED FOR CODE COMPLIANCE AND FAILED |
| | BY RYAN BROWN WITH THE FOLLOWING COMMENTS. |
| | |
| | NOTE: PAGE SP100-SITE PLAN - THIS LAYOUT DOES NOT MATCH |
| | THE REST OF THE PAGES. |
| | |
| | 1. 2017 WPB AMEND - 105.1/107.3 -- PAGE C4.0 INDICATES |
| | TWO SEPARATE METER CONNECTIONS. ONE FOR IRRIGATION AND |
| | ONE FOR THE POTABLE WATER. EACH WILL REQUIRED ITS OWN |
| | BACKFLOW PERMIT. THESE ARE REQUIRED TO BE APPLIED FOR |
| | PRIOR TO ISSUANCE OF THE PRIMARY PERMIT. YOU CAN SUBMIT |
| | AN APPLICATION "TBD" (TO BE DETERMINED) IF YOU DO NOT |
| | HAVE A CONTRACTOR SELECTED BY EMAILING A COMPLETED |
| | PERMIT APPLICATION TO [email protected]. AFTER |
| | YOU HAVE THE PERMIT(S) GENERATED, NOTIFY ME VIA EMAIL |
| | OR NOTE IN THE RESPONSE LETTER AND I WILL COMPLY THIS |
| | COMMENT. |
| | |
| | 2. 2017 WPB AMEND - 105.1/107.3 -- IRRIGATION WILL |
| | REQUIRE A SEPARATE PERMIT |
| | |
| | 3. 2017 WPB AMEND 107.3.5.3 (12) - PLEASE ADD A RISER |
| | IN ISOMETRIC FORM FOR PLUMBING REVIEW. A RISER IS |
| | ALWAYS REQUIRED. A PRELIMINARY REVIEW OF THE SANITARY |
| | FOLLOWS BUT WILL NEED TO HAVE THE ISOMETRIC FOR FULL |
| | REVIEW: |
| | A) PAGE P200B - POOL BATH AREA - 2020 FRC P3108.1 - THE |
| | KITCHENETTE CANNOT CONNECT INTO THE SHOWER FIXTURE |
| | DRAIN. IF A WET VENT SYSTEM IS BEING USED IN THE |
| | BATHROOM AREA, ANY OTHER FIXTURES WOULD NEED TO |
| | DISCHARGE DOWNSTREAM OF THE BATHROOM GROUP. |
| | B) PAGE P200B - POOL BATH AREA - 2020 FRC P3108.2.1 - |
| | IT APPEARS, BUT IS UNCLEAR THAT THE WATER CLOSET AND |
| | SHOWER ARE BOTH UPSTREAM OF THE VENTED FIXTURE'S |
| | (LAVATORY) CONNECTION. ONLY ONE FIXTURE WOULD BE |
| | ALLOWED UPSTREAM OF THE VENTED FIXTURE THAT CREATES THE |
| | WET VENT FOR THAT BATHROOM GROUP. |
| | C) PAGE P200B - POOL BATH AREA - 2020 FPC P3104.4 - THE |
| | PRIVATE WATER CLOSET HAS A DRYVENT THAT IS HORIZONTAL |
| | BELOW THE FLOOD RIM OF THE FIXTURE. A VENT SHALL RISE |
| | VERTICALLY TO 6" ABOVE THE FLOOD RIM OF THE FIXURE(S) |
| | SERVED. |
| | D) PAGE P200A - STAFF LOUNGE AREA - THE WATER CLOSET IS |
| | NOT VENTED TO CODE. |
| | E) PAGE P200A - KITCHEN AREA - 2020 FRC P3101.2.1 - IT |
| | IS UNCLEAR IF THE KITCHEN TRAPS ARE VENTED/STUDOR |
| | VENTED? |
| | THIS IS ALL I CAN SEE FOR NOW. PLEASE SUBMIT THE SECOND |
| | FLOOR PLAN AS WELL AS THE COMPLETE ISOMETRIC FOR THE |
| | SANITARY FOR REVIEW. INCLUDE THE CONTINUATION OF THE |
| | VENTING IN THE SANITARY ISOMETRIC |
| | F) PAGE 201A - 2017 WPB AMEND 107.3.5.3 (12) - IT |
| | APPEARS THE UPSTAIRS WATER CLOSET AND BATHTUB ARE |
| | MISSING FROM THE DRAWING. |
| | G)PAGE 201A - 2017 WPB AMEND 107.3.5.3 (12) - IN THE |
| | SAME AREA IT APPEARS ONE OF THE WYES IS FACING |
| | BACKWARDS. |
| | |
| | 4. 2017 WPB AMEND 107.3.5.3 (12) - THE SECOND FLOOR |
| | PLUMBING PLAN APPEARS TO BE MISSING. |
| | |
| | 5. PAGE 701 - 2017 WPB AMEND 107.3.5.3 (12) - THERE IS |
| | A NOTE ON THE WATER RISR-EAST THAT STATES "REFER TO |
| | P702" AND THERE IS NO PAGE 702. |
| | |
| | |
| | |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM. |
| | |
| | |
| | RYAN W. BROWN |
| | CHIEF PLUMBING INSPECTOR |
| | OFFICE: 561-805-6692 |
| | CELL: 561-517-4293 |
| | EMAIL: [email protected] |
| | |
| | |
| | V7 FPC - 2020 FLORIDA PLUMBING CODE |
| | V7 FGC - 2020 FLORIDA FUEL GAS |
| | V7 FRC - 2020 FLORIDA RESIDENTIAL BUILDING CODE |
| | V7 FAC - 2020 FLORIDA ACCESSIBILITY CODE |
| | V7 FEX - 2020 FLORIDA EXISTING BUILDING CODE |
| | V7 FEC - 2020 FLORIDA ENERGY CONSERVATION |
| | 2021 F.S. - 2021 FLORIDA STATUTES |
| | 2021 F.A.C. - 2021 FLORIDA ADMINISTRATIVE CODE |
| | 2017 WPB AMEND - 2017 WEST PALM BEACH AMENDMENTS TO THE |
| | FBC CHAPTER 1 |
| | |
| | |