2023-02-28 11:27:221ST REVIEW FMC
 PERMIT: 23021237
  
 CODES IN EFFECT: 2020
  
 FBC- FLORIDA BUILDING CODE
 FMC- FLORIDA MECHANICAL CODE
 FEC- FLORIDA ENERGY CONSERVATION
 FGC- FLORIDA FUEL GAS
 FEX- FLORIDA EXISTING BUILDING CODE
 FRC- FLORIDA RESIDENTIAL BUILDING CODE
 F.S.- FLORIDA STATUTES
 FAC- FLORIDA ACCESSIBILITY CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THE SUBMITTED MECHANICAL EQUIPMENT SIZING
 CALCULATIONS DESIGNED FOR 4 SYSTEMS, EACH BEING A
 NATURAL GAS FURNACE, DOES NOT MATCH THE MECHANICAL
 DRAWINGS THAT ARE DESIGNED WITH 22 AHU???S AND 12
 HP???S. THE MECHANICAL SIZING CALCULATIONS FBC 107.3.5
  
 2) SHEET M201-A: THE DRYERS APPEAR TO SHARE ONE SINGLE
 DRYER DUCT. PROVIDE A DETAIL OF THIS DESIGN SHOWING THE
 DUCT SIZES FOR THE SINGLE DRYERS AND ALSO THE DUCT
 AFTER THE 2 ARE JOINED. FRC M1502
  
 3) SHEET M201B: PROVIDE THE VENTILATION DETAILS FOR THE
 GENERATOR ROOM. WHERE IS THE INTAKE FOR THIS GENERATOR?
 FBC 107.3.5
  
 4) SHEET M202: EXPLAIN THE DAMPERS IN THE EXHAUST DUCT
 SYSTEM. FBC 107.3.5
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  