| 2023-02-28 11:27:22 | 1ST REVIEW FMC | | | PERMIT: 23021237 | | | | | | CODES IN EFFECT: 2020 | | | | | | FBC- FLORIDA BUILDING CODE | | | FMC- FLORIDA MECHANICAL CODE | | | FEC- FLORIDA ENERGY CONSERVATION | | | FGC- FLORIDA FUEL GAS | | | FEX- FLORIDA EXISTING BUILDING CODE | | | FRC- FLORIDA RESIDENTIAL BUILDING CODE | | | F.S.- FLORIDA STATUTES | | | FAC- FLORIDA ACCESSIBILITY CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) THE SUBMITTED MECHANICAL EQUIPMENT SIZING | | | CALCULATIONS DESIGNED FOR 4 SYSTEMS, EACH BEING A | | | NATURAL GAS FURNACE, DOES NOT MATCH THE MECHANICAL | | | DRAWINGS THAT ARE DESIGNED WITH 22 AHU???S AND 12 | | | HP???S. THE MECHANICAL SIZING CALCULATIONS FBC 107.3.5 | | | | | | 2) SHEET M201-A: THE DRYERS APPEAR TO SHARE ONE SINGLE | | | DRYER DUCT. PROVIDE A DETAIL OF THIS DESIGN SHOWING THE | | | DUCT SIZES FOR THE SINGLE DRYERS AND ALSO THE DUCT | | | AFTER THE 2 ARE JOINED. FRC M1502 | | | | | | 3) SHEET M201B: PROVIDE THE VENTILATION DETAILS FOR THE | | | GENERATOR ROOM. WHERE IS THE INTAKE FOR THIS GENERATOR? | | | FBC 107.3.5 | | | | | | 4) SHEET M202: EXPLAIN THE DAMPERS IN THE EXHAUST DUCT | | | SYSTEM. FBC 107.3.5 | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM. | | | | | | MICHAEL EDWARDS | | | MECHANICAL EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL. 33401 | | | 561-805-6728 | | | [email protected] | | | |
|