| Date |
Text |
| 2023-03-15 11:27:46 | |
| | |
| 2023-02-28 14:18:36 | 1ST GAS REVIEW |
| | |
| | THIS PLAN WAS REVIEWED FOR CODE COMPLIANCE AND FAILED |
| | BY RYAN BROWN WITH THE FOLLOWING COMMENTS. |
| | |
| | 1. 2017 WPB AMEND 107.3.5.3 (13) - PLEASE SUBMIT A GAS |
| | RISER DIAGRAM THAT INCLUDES ANY OF THE FOLLOWING |
| | APPLICABLE ITEMS. |
| | A) AN ISOMETRIC THAT INCLUDES - PIPE MATERIAL, LOCATION |
| | OF SHUT OFFS, PIPING LENGTHS, PIPE PRESSURES, LOCATION |
| | OF REGULATORS, BTU LOADS FROM EACH APPLIANCE, |
| | INDIVIDUAL SYSTEM SIZING WITH REFERENCES TO SIZING |
| | TABLES FROM THE CODE. |
| | B) A FLOOR PLAN THAT INCLUDES APPLIANCE LOCATIONS AND |
| | COMBUSTION AIR/MAKE UP AIR SIZING FOR EACH APPLIANCE |
| | WITHIN THE ROOM THAT CONTAINS IT. |
| | C) VENTING DETAILS FOR APPLIANCES THAT VENT TO THE |
| | OUTDOORS, INCLUDE DISTANCES FOR SEPARATION FROM THE |
| | VENT TERMINATIONS TO OPERABLE WINDOWS, AIR INTAKES, |
| | ETC. |
| | D) CHIMNEY DETAILS FOR THE FIREPLACES |
| | E) SPECS FOR THE APPLIANCES |
| | F) SPECIAL ATTENTION TO THE GENERATOR ROOM AND THE |
| | COMBUSTION AIR INTAKES, EXHUASTS, SEPARATION EXHAUST |
| | AND INTAKES WITH OTHER SYSTEMS. |
| | I) SPECIAL NOTE FOR THE GENERATOR EXHAUST - 2020 FRC |
| | R303.5.1 - RESIDENTIAL GAS GENERATOR EXHAUST |
| | TERMINATION MUST BE 10 FEET FROM ANY OPENING INTO THE |
| | STRUCTURE AND FROM ANY LOT LINE/POSSIBLE OPENING INTO |
| | ANY OTHER STRUCTURE. |
| | G) DETAILS FOR ANY SLEEVING REQUIRED FOR PENETRATIONS |
| | INTO THE STRUCTURE OR UNDER THE STRUCTURE. |
| | |
| | |
| | |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM. |
| | |
| | |
| | RYAN W. BROWN |
| | CHIEF PLUMBING INSPECTOR |
| | OFFICE: 561-805-6692 |
| | CELL: 561-517-4293 |
| | EMAIL: [email protected] |
| | |
| | |
| | V7 FPC - 2020 FLORIDA PLUMBING CODE |
| | V7 FGC - 2020 FLORIDA FUEL GAS |
| | V7 FRC - 2020 FLORIDA RESIDENTIAL BUILDING CODE |
| | V7 FAC - 2020 FLORIDA ACCESSIBILITY CODE |
| | V7 FEX - 2020 FLORIDA EXISTING BUILDING CODE |
| | V7 FEC - 2020 FLORIDA ENERGY CONSERVATION |
| | 2021 F.S. - 2021 FLORIDA STATUTES |
| | 2021 F.A.C. - 2021 FLORIDA ADMINISTRATIVE CODE |
| | 2017 WPB AMEND - 2017 WEST PALM BEACH AMENDMENTS TO THE |
| | FBC CHAPTER 1 |
| | |
| | |