| Plan Review Notes For Permit 23021237 |
| Permit Number |
23021237 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2023-03-15 11:30:00 | FLORIDA BUILDING CODE 2020 7TH EDITION | | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED | | | NFPA 70 2017 EDITION | | | | | | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW | | | | | | 1. PROVIDE LOAD CALCULATION FOR SERVICE IN ACCORDANCE | | | WITH NE 220. | | | | | | 2. PROVIDE AN ONE-LINE DIAGRAM SHOWING INFORMATION OF | | | SERVICE EQUIPMENT (SERVICE CONDUCTORS, SERVICE | | | OVERCURRENT PROTECTION, GROUNDED CONDUCTOR, EQUIPMENT | | | GROUNDING CONDUCTORS (EGC), MAIN PANEL AND SUBPANELS). | | | NEC 230, 250 | | | | | | 3. SERVICE RECEPTACLE PER NEC 210.63 OR IRC E3901.11 | | | THE RECEPTACLE MUST BE IN A READILY ACCESSIBLE LOCATION | | | FROM THE EQUIPMENT AND MUST BE GFCI-PROTECTED AS | | | APPLICABLE TO OUTDOOR RECEPTACLES AT DWELLING | | | OCCUPANCIES | | | | | | 4. AT LEAST ONE 120-VOLT, 20-AMPERE BRANCH CIRCUIT | | | SHALL BE INSTALLED TO SUPPLY RECEPTACLE OUTLETS IN | | | ATTACHED GARAGES AND IN DETACHED GARAGES WITH ELECTRIC | | | POWER. THIS CIRCUIT SHALL HAVE NO OTHER OUTLETS AS PER | | | NEC 210.11(C)(4) | | | | | | 5. SWIMMING POOL REQUIRES A SEPARATE PERMI NUMBER. | | | | | | END OF COMMENTS | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM. | | | | | | RUBEN PEREZ PERDOMO, P.E. | | | ELECTRICAL PLANS EXAMINER | | | 561-805-6738 | | | [email protected] |
|