Plan Review Notes
Plan Review Notes For Permit 23021237
Permit Number 23021237
Review Stop E
Sequence Number 1
Notes
Date Text
2023-03-15 11:30:00FLORIDA BUILDING CODE 2020 7TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED
 NFPA 70 2017 EDITION
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW
  
 1. PROVIDE LOAD CALCULATION FOR SERVICE IN ACCORDANCE
 WITH NE 220.
  
 2. PROVIDE AN ONE-LINE DIAGRAM SHOWING INFORMATION OF
 SERVICE EQUIPMENT (SERVICE CONDUCTORS, SERVICE
 OVERCURRENT PROTECTION, GROUNDED CONDUCTOR, EQUIPMENT
 GROUNDING CONDUCTORS (EGC), MAIN PANEL AND SUBPANELS).
 NEC 230, 250
  
 3. SERVICE RECEPTACLE PER NEC 210.63 OR IRC E3901.11
 THE RECEPTACLE MUST BE IN A READILY ACCESSIBLE LOCATION
 FROM THE EQUIPMENT AND MUST BE GFCI-PROTECTED AS
 APPLICABLE TO OUTDOOR RECEPTACLES AT DWELLING
 OCCUPANCIES
  
 4. AT LEAST ONE 120-VOLT, 20-AMPERE BRANCH CIRCUIT
 SHALL BE INSTALLED TO SUPPLY RECEPTACLE OUTLETS IN
 ATTACHED GARAGES AND IN DETACHED GARAGES WITH ELECTRIC
 POWER. THIS CIRCUIT SHALL HAVE NO OTHER OUTLETS AS PER
 NEC 210.11(C)(4)
  
 5. SWIMMING POOL REQUIRES A SEPARATE PERMI NUMBER.
  
 END OF COMMENTS
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
 RUBEN PEREZ PERDOMO, P.E.
 ELECTRICAL PLANS EXAMINER
 561-805-6738
 [email protected]