Plan Review Notes
Plan Review Notes For Permit 23021188
Permit Number 23021188
Review Stop B
Sequence Number 1
Notes
Date Text
2023-03-08 10:08:04TEMPORARY MEMBRANE STRUCTURES (TENTS)
  
 BUILDING PLAN REVIEW
  
 CHRISTOPHER S. THROOP, C.B.O., CFM
 PLANS EXAMINER II PX3169/SFP306
 INSPECTOR BN4338
 BUILDING OFFICIAL BU1635
 ASFPM CERTIFIED FLOODPLAIN MANAGER US-21-11935
 DEVELOPMENT SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 (561) 805-6726
 [email protected]
  
 CODES IN EFFECT:
 2020 FLORIDA BUILDING CODE, 7TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
 FBC SECTION 3103 TEMPORARY STRUCTURES
 F.S. 553.79 THRESHOLD STRUCTURES
  
 1ST REVIEW
  
 RESULTS: DENIED
  
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. FOR TEMPORARY MEMBRANE STRUCTURES (TENTS) WITH A
 SPAN OF 40 FEET OR GREATER IN ANY DIRECTION:
  
 A. PROVIDE DETAILS OF STRUCTURAL CONNECTIONS. INCLUDE
 BASEPLATE/TIEDOWN DETAILS.(REVIEWED AND PENDING RECEIPT
 OF WIND LOAD DESIGN CALC'S)
 B. PROVIDE STRUCTURAL EVALUATION PER FBC CHPT 16/ ASCE
 7-16 OF STRUCTURE. PROVIDE WIND LOAD DESIGN CRITERIA
 FOR ALL TENTS WITH A SPAN OF 40 FEET OR GREATER IN ANY
 DIRECTION.
  
 THESE DOCUMENTS SHALL BE REVIEWED, SIGNED AND SEALED BY
 A DESIGN PROFESSIONAL.
  
 NO EXCEPTIONS BY ORDER OF THE BUILDING OFFICIAL
  
 _______________________________________________________
 _________
  
 2. LAND BASED STRUCTURES A, B & C ARE POTENTIAL
 THRESHOLD STRUCTURES. PROVIDE THE OCCUPANCY RATING OF
 THESE THREE STRUCTURES. SEE COMMENTS UNDER THRESHOLD
 REVIEW.
  
 ***ADDITIONAL REQUIREMENTS***
 FOR TEMPORARY MEMBRANE STRUCTURES (TENTS) WITH AN
 ASSEMBLY OCCUPANCY CLASSIFICATION AS DEFINED IN THE
 FLORIDA BUILDING CODE WHICH EXCEEDS 5,000 SQ. FT. IN
 AREA AND AN OCCUPANT CONTENT OF GREATER THAN 500
 PERSONS.
  
 FLORIDA STATUTE 553.79 THREHOLD STRUCTURE MAY APPLY
  
 A. PROVIDE THRESHOLD INSPECTOR AGREEMENT ??? WILL BE
 PROVIDED TO APPLICANT
 B. PROVIDE THRESHOLD INSPECTION PLAN
 C. PROVIDE AFFIDAVIT ???CERTIFICATE OF CODE
 COMPLIANCE???
  
 3. PROVIDE THE CERTIFICATION OF FLAME RESISTANCE FOR
 ALL TEMPORARY MEMBRANE STRUCTURES.
 107.2 CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS
 SHALL BE IN ACCORDANCE WITH SECTIONS107.2.1 THROUGH
 107.2.5.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
 WHEN RESUBMITING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
  