| Date |
Text |
| 2023-03-24 09:43:27 | 2ND REVIEW FMC |
| | PERMIT: 23021157 |
| | |
| | CODES IN EFFECT: 2020 |
| | |
| | FBC- FLORIDA BUILDING CODE |
| | FMC- FLORIDA MECHANICAL CODE |
| | FEC- FLORIDA ENERGY CONSERVATION |
| | FGC- FLORIDA FUEL GAS |
| | FEX- FLORIDA EXISTING BUILDING CODE |
| | FRC- FLORIDA RESIDENTIAL BUILDING CODE |
| | F.S.- FLORIDA STATUTES |
| | FAC- FLORIDA ACCESSIBILITY CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) PROVIDE THE KEY PLAN ASKED FOR IN PREVIOUS REVIEW |
| | CYCLE. THERE IS AN OCCUPANCY CLASSIFICATION FOR EVERY |
| | BUILDING. PROVIDE A UL DETAIL FOR THE PENETRATION |
| | PROTECTION OF THIS WALL. FBC 107.3.5 |
| | |
| | 2) THE TERMINATION FOR THIS SMOKER GREASE DUCT SHALL |
| | MEET ALL THE REQUIREMENTS OF FMC 506.3.13.3 FOR |
| | CLEARANCES FROM THE BUILDING. PROVIDE A ROOF DRAWING |
| | THAT CLEARLY SHOWS THE TERMINATION MEETS THE FOLLOWING |
| | CODE SECTION: |
| | |
| | 506.3.13.3 TERMINATION LOCATION. EXHAUST OUTLETS SHALL |
| | BE LOCATED NOT LESS THAN 10 FEET (3048 MM) HORIZONTALLY |
| | FROM PARTS OF THE SAME OR CONTIGUOUS BUILDINGS, |
| | ADJACENT |
| | BUILDINGS AND ADJACENT PROPERTY LINES AND SHALL BE |
| | LOCATED NOT LESS THAN 10 FEET (3048 MM) ABOVE THE |
| | ADJOINING GRADE LEVEL. EXHAUST OUTLETS SHALL BE LOCATED |
| | NOT LESS THAN 10 FEET (3048 MM) HORIZONTALLY FROM OR |
| | NOT LESS THAN 3 FEET (914 MM) ABOVE AIR INTAKE OPENINGS |
| | INTO ANY BUILDING. |
| | |
| | EXCEPTION: EXHAUST OUTLETS SHALL TERMINATE NOT LESS |
| | THAN 5 FEET (1524 MM) HORIZONTALLY FROM PARTS OF THE |
| | SAME OR CONTIGUOUS BUILDING, AN ADJACENT BUILDING, |
| | ADJACENT PROPERTY LINE AND AIR INTAKE OPENINGS INTO A |
| | BUILDING WHERE AIR FROM THE EXHAUST OUTLET DISCHARGES |
| | AWAY FROM SUCH LOCATIONS. |
| | |
| | 3) THE H-2 SHEET WILL NEED THE EOR TO DIGITALLY SIGN |
| | THE DRAWING. FS 471/481 |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM. |
| | |
| | MICHAEL EDWARDS |
| | MECHANICAL EXAMINER |
| | 401 CLEMATIS STREET |
| | WEST PALM BEACH FL. 33401 |
| | 561-805-6728 |