2023-03-15 08:57:14AS PER SEC. 94-110, THIS SIGN IS CONSIDERED AN EXTERNAL
 SIGN BAND. AN EXTERNAL SIGN BAND MAY BE APPLIED ON THE
 FACADE OF EACH BUILDING PROVIDED THAT IT SHALL NOT
 EXCEED 36 INCHES IN HEIGHT BY 60 PERCENT OF THE
 APPLICABLE STOREFRONT WIDTH. SIGNAGE MAY BE PERMITTED
 ON AWNINGS OR CANOPIES, BUT SHALL BE CONSIDERED AS
 SQUARE FOOTAGE AGAINST THE ALLOWABLE SIGNAGE AREA. THE
 SIGN BAND SHALL BE LOCATED WITHIN THE FIRST TWO STORIES
 OF THE BUILDING.
  
 ON SHEET 002 ENGINEERING, THE SIGN PROJECTS FURTHER IN
 THE SIDEWALK COMPARE TO THE AWNING, PLEASE ALIGN THE
 SIGN WITH THE AWNING SO THE SIGN IS PLACED AT THE SAME
 VERTICAL AND HORIZONTAL LINE AS THE AWNING.
  
 PLEASE NOTE, ALL INSTALLATION COMPONENTS OR HANGING
 DEVICES SUCH AS, BUT NOT LIMITED TO, FASTENERS, CLIPS,
 BOLTS, ETC., SHALL BE OF NON-CORROSIVE, STAINLESS
 STEEL, ALUMINUM, BRASS OR BRONZE; CARBON BEARING STEEL
 SHALL BE OF NONFERROUS METAL OF QUALITY MATERIAL AND
 FINISH. ALL FASTENERS SHALL BE CONCEALED. ALL SIGNAGE
 SHALL HAVE AN INDIVIDUAL CIRCUIT AND BE CONTROLLED BY A
 TIME CLOCK. EXPOSED CONDUIT OR ELECTRICAL WIRING IS
 PROHIBITED. EXPOSED RACEWAYS, TRANSFORMERS, BALLASTS,
 AND ELECTRICAL WIRING ARE PROHIBITED. CHANNEL OR
 CUT-LETTER SIGNAGE IS RECOMMENDED.
  