2023-04-11 08:11:01COMPLY TO SIGNATURE COMMENT.
 PLEASE UPDATE SCOPE OF WORK ON COVER PAGE FOR UNIT
 MENTIONED IN THIS PARTICULAR PERMIT INCLUDING ALL
 TRADES.
 THIS IS UNIT 1203 AND YOU ARE USING THE SAME COVER PAGE
 FOR BOTH 1203 AND 1204.
 THE ENTRANCE DOOR IN UNIT 1203 IS PART OF THE ELEVATOR
 LOBBY VESTIBULE. THAT PORTION OF THE UPDATED WALL
 SHOULD BE THE SAME FIRE RATING AS THE REST OF THE WALL
 IN THE EXISTING ELEVATOR LOBBY.
  
 THE PORTION THAT IS IN THE KITCHEN ADJACENT TO THE
 ELEVATOR VESTIBULE CAN BE AS PER THE INTERIOR PARTION
 YOUR ARE SHOWIONG ON PAGE A2.
 PROVIDE WALL TAGS AND WALL TYPE SECTIONS FOR BOTH TYPES
 AS PART OF UNIT 1203 PERMIT.
  
  
 DO NOT HESITATE TO CONTACT ME IF YOU HAVE ANY QUESTIONS
 OR CONCERNS,
  
 THANK YOU.
  