Plan Review Notes
Plan Review Notes For Permit 23021107
Permit Number 23021107
Review Stop M
Sequence Number 1
Notes
Date Text
2023-04-13 11:35:031ST REVIEW FMC
 PERMIT: 23021107
  
 CODES IN EFFECT: 2020
  
 FBC- FLORIDA BUILDING CODE
 FMC- FLORIDA MECHANICAL CODE
 FEC- FLORIDA ENERGY CONSERVATION
 FGC- FLORIDA FUEL GAS
 FEX- FLORIDA EXISTING BUILDING CODE
 FRC- FLORIDA RESIDENTIAL BUILDING CODE
 F.S.- FLORIDA STATUTES
 FAC- FLORIDA ACCESSIBILITY CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PROVIDE THE LIKE FOR LIKE CHANGE OUT FORM FOR THE
 AHU THAT IS TO BE CHANGED OUT. THIS SHOULD SHOW THE
 INFORMATION FOR THE EXISTING UNIT AND THE INFORMATION
 FOR THE NEW UNIT, INCLUDING THE NEW SEER2 RATING OF THE
 REPLACEMENT UNIT.
  
 2) DOCUMENTS SUBMITTED WILL NEED THE DESIGNERS DIGITAL
 SIGNATURE. FS 471/481
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  