Plan Review Notes
Plan Review Notes For Permit 23021107
Permit Number 23021107
Review Stop E
Sequence Number 1
Notes
Date Text
2023-04-10 14:41:41FLORIDA BUILDING CODE 2020 7TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED
 NFPA 70 2017 EDITION
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW
  
 1. PROVIDE PANEL SCHEDULE IN ACCORDANCE WITH NEC
 408.4(B).
  
 2. SMOKE ALARMS (SMOKE DETECTION) SYSTEM AND CO (CARBON
 MONOXIDE) DETECTION SYSTEM SHALL BE PROVIDED IN
 ACCORDANCE WITH NFPA 72, FBC 907, IRC 314, IRC 315.
  
 END OF COMMENTS
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
 RUBEN PEREZ PERDOMO, P.E.
 ELECTRICAL PLANS EXAMINER
 561-805-6738
 [email protected]
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved