| Date |
Text |
| 2023-06-23 16:42:52 | 2ND REVIEW FBC-2020 RES. GAS |
| | PERMIT- 23021087 |
| | 6/23/23 |
| | |
| | CODES IN EFFECT: |
| | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION |
| | 2020 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. 2ND REQUEST FOR GAS PLANS. |
| | THE GAS CONTRACTOR HAS SUBMITTED A GAS SUB-PERMIT |
| | APPLICATION (23040242) WHICH REQUIRES PLANS TO BE |
| | SUBMITTED UNDER THIS MASTER PERMIT. PLEASE SUBMIT THE |
| | DRAWINGS PER THE COMMENTS BELOW. |
| | |
| | 1) SHEET A2: THE PLAN SHOWS A NEW GAS FIRED TANKLESS |
| | WATER HEATER MOUNTED ON THE REAR WALL OF THE HOUSE. |
| | PLEASE PROVIDE A GAS PIPING RISER DIAGRAM PER SEC. |
| | 107.3.5.3 WPB. THE RISER SHALL INCLUDE ALL NEW AND |
| | EXISTING PIPING AT THE RESIDENCE IN COMPLIANCE WITH |
| | SECS. G2412.3 & G2412.4 FBC RES. REFER TO FBC RES. |
| | CHAPTER 24 FUEL GAS. THE RISER SHALL INDICATE: |
| | |
| | A) TYPE OF GAS- NATURAL OR LP. |
| | B) DELIVERY PRESSURE AT THE METER. |
| | C) TOTAL BTU LOAD AND INDIVIDUAL APPLIANCE BTU LOADS. |
| | D) TYPES AND SIZES OF PIPING. |
| | E) TOTAL DEVELOPED LENGTH OF THE SYSTEM FROM THE METER |
| | TO THE MOST REMOTE APPLIANCE OUTLET. |
| | F) BRANCH AND CUT PIPE LENGTH MEASUREMENTS. |
| | G) LOCATIONS OF REGULATORS, SHUTOFF VALVES. |
| | H) OUTLET PRESSURES AT REGULATORS. |
| | I) LOCATIONS AND TYPES OF PIPE SLEEVES. |
| | K) PIPE SIZING TABLES. |
| | . |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | CHRISTOPHER L. COLE |
| | MECHANICAL/PLUMBING PLANS EXAMINER |
| | 401 CLEMATIS STREET |
| | WEST PALM BEACH FL 33401 |
| | 561-805-6719 |
| | [email protected] |
| | |