Plan Review Notes For Permit 23021085
Permit Number 23021085
Review Stop G
Sequence Number 1
Notes
Date Text
2023-03-06 14:49:181ST REVIEW FBC-2020 RES. GAS
 PERMIT- 23021085
 3/6/23
  
 CODES IN EFFECT:
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION
 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET P-0.1: A COMPLETE GAS PIPING PLAN AND RISER
 DRAWING IS REQUIRED WHICH INCLUDES THE EXISTING
 INTERIOR GAS PIPING AND APPLIANCE LOADS- SEC. G2412.3 &
 G2412.4 FBC RES. REVISE THE DRAWINGS TO SHOW THE
 FOLLOWING ITEMS:
 A) TYPE AND SIZE OF THE MAIN SUPPLY PIPE AT THE METER
 AND THE INTERIOR PIPING POINT OF CONNECTION TO THE
 MAIN.
 B) TYPE AND SIZE OF RISER PIPE FROM THE PE TO THE MAIN.
 C) REVISE THE GAS SCHEDULE TO INCLUDE THE EXISTING
 APPLIANCE LOADS AND THE TOTAL LOAD.
  
 2) P-0.1: PLEASE SHOW THE CLEARANCE DISTANCE FROM THE
 GENERATOR EXHAUST TO MECHANICAL AND GRAVITY AIR INTAKES
 INTO THE BUILDING INCLUDING OPERABLE WINDOWS AND DOORS.
 PLEASE NOTE A MINIMUM 10 FT. CLEARANCE IS REQUIRED.
  
 3) P-0.1: PLEASE PLACE A NOTE ON THE PLAN INDICATING A
 SEPARATE PERMIT IS REQUIRED FOR THE NEW GENERATOR- SEC.
 107.2.1 WPB.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  