Plan Review Notes
Plan Review Notes For Permit 23021064
Permit Number 23021064
Review Stop P
Sequence Number 1
Notes
Date Text
2023-02-23 10:02:061ST PLUMBING REVIEW
  
 THIS PLAN WAS REVIEWED FOR CODE COMPLIANCE AND FAILED
 BY RYAN BROWN WITH THE FOLLOWING COMMENTS.
  
 1. 2020 FRC P3108.1 - ON THE RISER THAT INCLUDES THE
 KITCHEN, THE WATER CLOSET IS CONNECTED TO THE
 HORIZONTAL DRAIN WITHOUT A VENT.
  
 2. 2020 FRC P3108.2.1 - ON THE BATHROOM RISER WITHOUT
 THE KITCHEN, THE TUB AND WATER CLOSET ARE BOTH UPSTREAM
 OF THE VENTED FIXTURE CONNECTION. ONLY ONE IS ALLOWED
 TO BE UPSTREAM OF THE VENTED FIXTURE'S CONNECTION TO
 THE HORIZONTAL WET VENT.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
  
 RYAN W. BROWN
 CHIEF PLUMBING INSPECTOR