Plan Review Notes
Plan Review Notes For Permit 23021063
Permit Number 23021063
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2023-02-23 12:53:15THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 1) THERE IS AN INDICATION NO CLEAR INDICATION OF AN
 EMEGENCY DISCONNECT REMOTELY LOCATED.
  
 FOR THE OFFICIAL RECORD, AND PER NFPA 70, PLEASE
 PROVIDE THE LOCATION OF AN EMERGECNY DISCONNECT WITH
 PROPER SIGNAGE FOR 1ST RESPONDERS IN THE EVENT OF
 EMERGECNY.
  
  
 2) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
 3) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  