| 2023-03-10 14:46:29 | ELECTRIC REVIEW FAILED |
| | |
| | 1) VALUE FOR WORK STATED ON PERMIT APPLICATION APPEARS |
| | LOW. PROVIDE A BREAKDOWN OF ALL MATERIALS AND LABOR, |
| | OR, AT YOUR DISCRETION, PROVIDE A SIGNED CONTRACTOR |
| | PROVIDE A REASONABLE VALUE. WPB F.B.C. 109.3 |
| | |
| | FBC 109.3 THE APPLICANT FOR A PERMIT SHALL PROVIDE AN |
| | ESTIMATED PERMIT VALUE AT TIME OF APPLICATION. PERMIT |
| | VALUATIONS SHALL INCLUDE TOTAL VALUE OF WORK, INCLUDING |
| | MATERIALS AND LABOR, FOR WHICH THE PERMIT IS BEING |
| | ISSUED, SUCH AS ELECTRICAL, GAS, MECHANICAL, PLUMBING |
| | EQUIPMENT AND PERMANENT SYSTEMS. IF, IN THE OPINION OF |
| | THE BUILDING OFFICIAL, THE VALUATION IS UNDERESTIMATED |
| | ON THE APPLICATION, THE PERMIT SHALL BE DENIED, UNLESS |
| | THE APPLICANT CAN SHOW DETAILED ESTIMATES TO MEET THE |
| | APPROVAL OF THE BUILDING OFFICIAL. FINAL BUILDING |
| | PERMIT VALUATION SHALL BE SET BY THE BUILDING OFFICIAL |
| | |
| | 2) NO SECIFICATIONS WERE PROVIDED FOR THE TESLA SUPER |
| | CHARGER CABINETS. PLEASE PROVIDE SPECIFICATIONS FOR |
| | THESE SUPER CHARGER CABINETS. PLEASE ENSURE THEY |
| | PROVIDE DISCONNECTION AND OVER CURRENT PROTECTION FOR |
| | EACH CHARGING POST CIRCUIT. NEC 240.4 AND NEC 625.43 |
| | |
| | 240.4 PROTECTION OF CONDUCTORS. |
| | CONDUCTORS, OTHER THAN FLEXIBLE CORDS, FLEXIBLE CABLES, |
| | AND FIXTURE WIRES, SHALL BE PROTECTED AGAINST |
| | OVERCURRENT IN ACCORDANCE WITH THEIR AMPACITIES |
| | |
| | 625.43 DISCONNECTING MEANS. |
| | FOR EQUIPMENT RATED MORE THAN 60 AMPERES OR MORE THAN |
| | 150 VOLTS TO GROUND, THE DISCONNECTING MEANS SHALL BE |
| | PROVIDED AND INSTALLED IN A READILY ACCESSIBLE |
| | LOCATION. THE DISCONNECTING MEANS SHALL BE LOCKABLE |
| | OPEN IN ACCORDANCE WITH 110.25. |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. |
| | |
| | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2020 7TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE 2020 7TH ED. |
| | FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020 |
| | 7TH EDITION |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 |
| | 7TH EDITION |
| | FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION |
| | NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE |
| | FS = FLORIDA STATUTES |
| | |
| | V/R, |
| | |
| | MICHAEL PETERSON |
| | ELECTRICAL PLANS EXAMINER |
| | [email protected] |
| | 561-805-6746 |
| | |
| | |