| 2023-02-27 16:25:41 | 1ST REVIEW FMC | | | PERMIT: 23021045 | | | | | | CODES IN EFFECT: 2020 | | | | | | FBC- FLORIDA BUILDING CODE | | | FMC- FLORIDA MECHANICAL CODE | | | FEC- FLORIDA ENERGY CONSERVATION | | | FGC- FLORIDA FUEL GAS | | | FEX- FLORIDA EXISTING BUILDING CODE | | | FRC- FLORIDA RESIDENTIAL BUILDING CODE | | | F.S.- FLORIDA STATUTES | | | FAC- FLORIDA ACCESSIBILITY CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) THE MECHANICAL SYSTEMS WILL BE REQUIRED TO MEET THE | | | NEW FEDERAL SEER2 REQUIREMENTS. PROVIDE THE MANUAL J | | | SHOWING THE SEER2 RATINGS. | | | | | | 2) THE SUBMITTAL DID NOT INCLUDE THE MECHANICAL | | | DRAWINGS. PROVIDE THE MECHANICAL DRAWINGS. FBC 107.3.5 | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM. | | | | | | MICHAEL EDWARDS | | | MECHANICAL EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL. 33401 | | | 561-805-6728 | | | [email protected] | | | |
|