| 2023-02-27 10:17:57 | 1ST REVIEW FBC-2020 RES. GAS |
| | PERMIT- 23021045 |
| | 2/27/23 |
| | |
| | CODES IN EFFECT: |
| | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION |
| | 2020 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) SHEET A-1: THE FLOOR PLAN SHOWS MULTIPLE GAS |
| | APPLIANCES INCLUDING TWO TANKLESS WATER HEATERS, POOL |
| | HEATER, RANGE, DRYER AND BBQ. PLEASE PROVIDE A GAS |
| | RISER DRAWING AND GAS PLANS IN COMPLIANCE WITH SEC. |
| | 107.3.5.3 WPB. |
| | ***PLEASE NOTE IF GAS FOR THE PROJECT IS PREFERRED TO |
| | BE UNDER A SEPARATE PERMIT, PLEASE SEND AN EMAIL TO |
| | [email protected] AND I WILL CHANGE THE FAILED (F) REVIEW |
| | RESULT TO NOT REQUIRED (N). |
| | |
| | 2) GAS RISER SUBMITTAL REQUIREMENTS PER SEC. G2413.2 & |
| | G2413.3 FBC RES. |
| | A) TYPE OF GAS- NATURAL OR LP. |
| | B) DELIVERY PRESSURE AT THE METER. |
| | C) TOTAL BTU LOAD AND INDIVIDUAL APPLIANCE BTU LOADS. |
| | D) TYPES AND SIZES OF PIPING. |
| | E) TOTAL DEVELOPED LENGTH OF THE SYSTEM FROM THE METER |
| | TO THE MOST REMOTE APPLIANCE OUTLET. |
| | F) BRANCH AND CUT PIPE LENGTH MEASUREMENTS. |
| | G) LOCATIONS OF REGULATORS, SHUTOFF VALVES. |
| | H) OUTLET PRESSURES AT REGULATORS. |
| | I) LOCATIONS AND TYPES OF PIPE SLEEVES. |
| | K) PIPE SIZING TABLES. |
| | |
| | 3) GAS PLANS: THE REQUIRED PLANS SHALL ADDRESS THE |
| | FOLLOWING ITEMS: |
| | A) THE TANKLESS WATER HEATERS APPEAR TO BE IN CLOSE |
| | PROXIMITY OF TWO WINDOWS WITHIN 4FT. OF THE HEATER |
| | EXHAUST. PLEASE VERIFY THE WINDOWS ARE FIXED AND DO NOT |
| | OPEN INTO THE BUILDING OR RELOCATE THE HEATERS- SECS. |
| | G2427.8 & G2448.1 FBC RES. |
| | B) COMBUSTION AIR FOR THE COOKTOP AND DRYER. PLEASE |
| | INDICATE HOW THE AIR IS BEING SUPPLIED AND PROVIDE |
| | CALCULATIONS- SEC. G2407.1 FBC RES. |
| | C) CONCERNING THE GAS BBQ IN THE LANAI PLEASE NOTE THAT |
| | TYPICAL MANUFACTURER'S SPECIFICATIONS AND INSTALLATION |
| | MANUALS WILL PROVIDE CLEARANCE DISTANCES FROM THE GRILL |
| | TO COMBUSTIBLE MATERIAL AND MAY ALSO REQUIRED |
| | INSTALLATION OF A EXHAUST HOOD. PLEASE REVIEW THE |
| | GUIDELINES AND PROVIDE NOTES AND DETAILS ON THE PLAN IF |
| | REQUIRED- SEC. 2447.1 FBC RES. |
| | D) PLEASE NOTE A SEPARATE PERMIT IS REQUIRED FOR THE |
| | POOL HEATER. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |