2023-02-27 10:17:571ST REVIEW FBC-2020 RES. GAS
 PERMIT- 23021045
 2/27/23
  
 CODES IN EFFECT:
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION
 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET A-1: THE FLOOR PLAN SHOWS MULTIPLE GAS
 APPLIANCES INCLUDING TWO TANKLESS WATER HEATERS, POOL
 HEATER, RANGE, DRYER AND BBQ. PLEASE PROVIDE A GAS
 RISER DRAWING AND GAS PLANS IN COMPLIANCE WITH SEC.
 107.3.5.3 WPB.
 ***PLEASE NOTE IF GAS FOR THE PROJECT IS PREFERRED TO
 BE UNDER A SEPARATE PERMIT, PLEASE SEND AN EMAIL TO
 [email protected] AND I WILL CHANGE THE FAILED (F) REVIEW
 RESULT TO NOT REQUIRED (N).
  
 2) GAS RISER SUBMITTAL REQUIREMENTS PER SEC. G2413.2 &
 G2413.3 FBC RES.
 A) TYPE OF GAS- NATURAL OR LP.
 B) DELIVERY PRESSURE AT THE METER.
 C) TOTAL BTU LOAD AND INDIVIDUAL APPLIANCE BTU LOADS.
 D) TYPES AND SIZES OF PIPING.
 E) TOTAL DEVELOPED LENGTH OF THE SYSTEM FROM THE METER
 TO THE MOST REMOTE APPLIANCE OUTLET.
 F) BRANCH AND CUT PIPE LENGTH MEASUREMENTS.
 G) LOCATIONS OF REGULATORS, SHUTOFF VALVES.
 H) OUTLET PRESSURES AT REGULATORS.
 I) LOCATIONS AND TYPES OF PIPE SLEEVES.
 K) PIPE SIZING TABLES.
  
 3) GAS PLANS: THE REQUIRED PLANS SHALL ADDRESS THE
 FOLLOWING ITEMS:
 A) THE TANKLESS WATER HEATERS APPEAR TO BE IN CLOSE
 PROXIMITY OF TWO WINDOWS WITHIN 4FT. OF THE HEATER
 EXHAUST. PLEASE VERIFY THE WINDOWS ARE FIXED AND DO NOT
 OPEN INTO THE BUILDING OR RELOCATE THE HEATERS- SECS.
 G2427.8 & G2448.1 FBC RES.
 B) COMBUSTION AIR FOR THE COOKTOP AND DRYER. PLEASE
 INDICATE HOW THE AIR IS BEING SUPPLIED AND PROVIDE
 CALCULATIONS- SEC. G2407.1 FBC RES.
 C) CONCERNING THE GAS BBQ IN THE LANAI PLEASE NOTE THAT
 TYPICAL MANUFACTURER'S SPECIFICATIONS AND INSTALLATION
 MANUALS WILL PROVIDE CLEARANCE DISTANCES FROM THE GRILL
 TO COMBUSTIBLE MATERIAL AND MAY ALSO REQUIRED
 INSTALLATION OF A EXHAUST HOOD. PLEASE REVIEW THE
 GUIDELINES AND PROVIDE NOTES AND DETAILS ON THE PLAN IF
 REQUIRED- SEC. 2447.1 FBC RES.
 D) PLEASE NOTE A SEPARATE PERMIT IS REQUIRED FOR THE
 POOL HEATER.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  