Plan Review Notes
Plan Review Notes For Permit 23021045
Permit Number 23021045
Review Stop B
Sequence Number 1
Notes
Date Text
2023-03-14 18:51:11RESIDENTIAL (R3) BUILDING REVIEW COMMENTS
 CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS.
 PERMIT #23021045
 348 POTTER RD
  
 1- LOT DRAINAGE. PROPOSED WORK AFFECTS THE LOT
 DRAINAGE. PROVIDE DRAINAGE PLAN SHOWING HOW THE SURFACE
 DRAINAGE IS KEPT WITHIN THE LOT AND NOT DIVERTED TO
 ADJACENT PROPERTIES. PROVIDE DRAINAGE PLAN SHOWING
 COMPLIANCE WITH THE FOLLOWING SECTIONS: R401.3
 FBC-RESIDENTIAL. SEC. 107.2.5 CITY AMENDMENTS AND SEC.
 110.9 CITY AMENDMENTS.
 NOTE: DRAINAGE PLAN TO SHOW THE EXISTING AND PROPOSED
 GRADE ELEVATIONS SHOWING HOW KEEPING WATER AWAY FROM
 ADJACENT PROPERTIES.
  
 2- BEDROOM EGRESS WINDOWS ON WINDOW SCHEDULE ON SHEET
 A-2 ARE NOT CLEAR. SOME WINDOWS ARE IDENTIFIED AS
 EGRESS UNDER THE TYPE COLUMN, SOME WINDOWS ARE
 IDENTIFIED AS EGRESS UNDER THE NOTES COLUMN AND WINDOWS
 FOR BEDROOM #3 ARE NOT SPECIFIED AS EGRESS. REVISE AS
 REQUIRED. CLEARLY IDENTIFY EGRESS WINDOW FOR EACH
 BEDROOM. SEC. 107.2.1 CITY AMENDMENTS. SEC. R310.2.1
 FBC-RESIDENTIAL.
 CLARIFY WHAT IS "T.G." AND "F.G" SPECIFIED UNDER THE
 TYPE COLUMN? SEC. 107.2.1 CITY AMENDMENTS.
  
 3- PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR
 STAIRWAY CONSTRUCTION: DIMENSIONS, RISERS, TREADS,
 NOSING, HANDRAILS, GUARDRAILS, ETC. SHOWING COMPLIANCE
 WITH SEC. R311.7 FBC-RESIDENTIAL.
  
 4- MASTER BATHROOM TOILET ROOM NEEDS A DOOR THAT
 PROVIDES 29" MIN. CLEAR OPENING AS REQUIRED BY SEC.
 R320.1.1 FBC-RESIDENTIAL.
  
 5- PROVIDE DETAILS/SPECIFICATIONS FOR STAIRWAY
 FIREBLOCKING AS REQUIRED BY SEC. R302.11
 FBC-RESIDENTIAL.
  
 6- PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR
 DRAFSTOPPING IN SECOND FLOOR AREAS AS REQUIRED BY SEC.
 R302.12 FBC-RESIDENTIAL.
  
 7- PROVIDE DETAILS AND SPECIFICATIONS FOR DECORATIVE
 SHUTTERS CONSTRUCTION AND INSTALLATION. SPECIFY
 FASTENING. SEC. R301.2.1 FBC-RESIDENTIAL.
  
 8- HOUSE IS DESIGNED WITH UNVENTED ATTIC. ENGINEER IS
 SPECIFYING SPRAY FOAM INSULATION. PROVIDE ICC
 EVALUATION REPORT FOR THE FOAM INSULATION TO VERIFY
 COMPLIANCE WITH SEC. R316 FBC-RESIDENTIAL.
 NOTE: ENGINEER OF RECORD TO REVIEW AND APPROVE THE
 REPORT IN WRITING PRIOR TO SUBMITTAL TO THIS OFFICE.
  
 9- BUILDING THERMAL ENVELOPE. ENGINEER OF RECORD NEEDS
 TO DEPICT THE BUILDING THERMAL ENVELOPE. NEED TO
 SPECIFY INSULATION MATERIALS AND THEIR R-VALUES.(ROOF,
 WALLS, RAISED FLOOR ABOVE GARAGE, ETC.) AS REQUIRED BY
 SEC. R103.2 FBC-ENERGY CONSERVATION.
  
 10- PROVIDE STRUCTURAL BUCK DETAIL AND FASTENING
 SPECIFICATIONS FOR NEW OVERHEAD GARAGE DOOR. SPECIFY
 ANCHOR TYPE, SIZE AND SPACING NOT PER PRODUCT APPROVAL.
 SEC. R301.1 FBC-RESIDENTIAL.
  
 11- PROVIDE DOOR (SWING AND SLIDING GLASS
 DOORS)STRUCTURAL BUCK DETAIL SHOWING COMPLIANCE WITH
 SEC. R609.7.2.1 FBC-RESIDENTIAL. SPECIFY STRUCTURAL
 BUCK SIZE AND FASTENING NOT PER PRODUCT APPROVAL.
 NOTE: STRUCTURAL BUCK NEEDS TO PROVIDE FULL SUPPORT TO
 THE DOOR FRAME AS REQUIRED BY SEC. R609.7.2.1
 FBC-RESIDENTIAL.
  
 12- ROOF ZONE DIAGRAM ON SHEET S-4. REVISE EDGE STRIP
 DIMENSION. THE MINIMUM DIMENSION IS 4'-0" NOT 3'-0" AS
 REQUIRED BY NOTE "A" ON FIGURE R301.2(7)
 FBC-RESIDENTIAL. REVISE AS REQUIRED.
  
 13- PRODUCT APPROVALS:
 PROVIDE PRODUCT APPROVAL AS REQUIRED BY FAC 61G20-3.001
 FOR:
 (NOTE: THIS MAY BE SUBMITTED LATER AS A DEFERRED
 SUBMITTAL. CONTRACTOR TO ADVISE IF SUBMITTING NOW OR
 LATER AS A DEFERRED SUBMITTAL).
 A)ENTRY DOOR AS SPECIFIED ON PLANS.
  
 B)GARAGE EXTERIOR SWING DOOR AS SPECIFIED ON PLANS.
  
 C)SLIDING GLASS DOORS AS SPECIFIED ON PLANS.
  
 D)CASEMENT WINDOW SIZE SPECIFIED FOR THE OFFICE.
  
 E)HURRICANE SHUTTERS IF DOORS AND WINDOWS DON'T HAVE
 IMPACT GLAZING. AND, PROVIDE COMPLETE INSTALLATION
 SCHEDULE. SEE CITY SAMPLE.
  
 F)ROOF TILE. NOTE: CLEARLY MARK ADHESIVE PADDY SIZE ON
 THE NOA 22-0714.13 SUBMITTED TO VERIFY COMPLIANCE WITH
 THE DESIGN PRESSURES OF SEC R301.2.1 FBC-RESIDENTIAL.
  
 G)ROOF TILE UNDERLAYMENT: NOTE: CLEARLY MARK ON NOA
 21-1217.02 SUBMITTED WHICH POLYGLASS POLYSTICK
 UNDERLAYMENT IS GOING TO BE USED.
  
 H)HIP & RIDGE METAL SUPPORT TO BE USED.
  
 14- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ABOVE PRODUCT APPROVALS AS
 REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS.
  
 15- SHOW ON PLANS CARBON MONOXIDE ALARMS WITHIN 10 FEET
 OF EACH BEDROOM ON THE SECOND FLOOR AS REQUIRED BY SEC.
 R315.1 FBC-RESIDENTIAL.
  
 16- ENERGY CALCULATIONS:
 A)THE BUILDING'S OWNER, THE OWNER'S ARCHITECT, OR OTHER
 AUTHORIZED AGENT LEGALLY DESIGNATED BY THE OWNER SHALL
 CERTIFY AT THE OWNER/AGENT LINE AT THE BOTTOM OF FORM
 THAT THE BUILDING IS IN COMPLIANCE WITH THE CODE, AS
 PER SECTION 553.907, FLORIDA STATUTES, PRIOR TO
 RECEIVING THE PERMIT TO BEGIN CONSTRUCTION OR
 RENOVATION AS REQUIRED BY SECTION R103.1.1.2 FBC-ENERGY
 CONSERVATION.
  
 B)PROVIDE COMPLETE INFORMATION ON TOP OF FORM,
 INCLUDING OWNER NAME, BUILDER NAME (IF AVAILABLE),
 CORRECT PERMIT OFFICE (CITY OF WEST PALM BEACH NOT PALM
 BEACH COUNTY), JURISDICTION NUMBER (THIS JURISDICTION
 IS 604700). SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION.
  
 C)CONDITIONED FLOOR AREA SPECIFIED ON ITEM #6 ON PAGE 1
 DOESN'T MATCH PLANS. REVISE AS REQUIRED TO MATCH. SEC.
 R101.5.1.1.2 FBC-ENERGY CONSERVATION.
  
 D)ITEM #10(B) ON PAGE 1 IS INCORRECT. THERE IS NOT WOOD
 FRAME WALL BETWEEN THE GARAGE AND THE MAIN HOUSE. SEE
 PLANS AND REVISE AS REQUIRED. SEC. R101.5.1.1.2
 FBC-ENERGY CONSERVATION.
  
 E)PROVIDE THE NAME OF THE PERSON DOING THE CALCULATIONS
 AS REQUIRED BY SEC. R405.4.2.1 FBC-ENERGY CONSERVATION.
  
 F)SPACES INFORMATION ON PAGE 2 IS MISSING THE NUMBER OF
 OCCUPANTS. PROVIDE INFORMATION. WHY THERE ARE "0"
 OCCUPANTS IN A FIVE BEDROOM HOUSE?. REVISE AS REQUIRED.
 SEC. R101.5.1.1.2 FBC- ENERGY CONSERVATION.
  
 G)REVISE WINDOWS AREA, SIZE AND WINDOWS OVERHANG DEPTH
 AND SEPARATION TO MATCH PLANS. SEE PLANS AND EXTERIOR
 ELEVATIONS. SEC. R101.5.1.1.2 FBC- ENERGY CONSERVATION.
  
 H)BUILDER TO COMPLETE THE ENERGY PERFORMANCE LEVEL
 (EPL) DISPLAY CARD. SEC. R405.4.3 FBC-ENERGY
 CONSERVATION.
  
 17- VALUATION DECLARED IN THE PERMIT APPLICATION IS TOO
 LOW. VALUATION TO INCLUDE ALL LABOR, MATERIALS,
 CONTRACTOR'S OVERHEAD AND PROFIT AND DESIGN
 PROFESSIONAL FEES AS REQUIRED BY SEC. 109.3 CITY
 AMENDMENTS. VALUATION UPDATED TO $817684.00. OWES
 $2273.53.
  
 WHEN RESUBMITTING, A TRANSMITTAL LETTER LISTING THE
 ORIGINAL REVIEW COMMENT WITH A DESCRIPTION OF WHERE AND
 HOW THE COMMENT WAS ADDRESSED WILL HELP TO EXPEDITE THE
 REVIEW PROCESS. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER