| 2023-07-17 14:50:36 | ELECTRIC REVIEW FAILED |
| | PROVIDED A WRITTEN NARRATIVE HOW THE BELOW COMMENTS |
| | WILL BE ADDRESSED. |
| | 1) SITE PLAN IDENTIFYING ALL STRUCTURES. FBC 107.2 NOT |
| | ADDRESSED |
| | |
| | 2) A NARRATIVE WORK SCOPE FOR EACH STRUCTURE. FBC 107.2 |
| | PARTIALLY ADDRESSED. PLANS STATE REPLACE WIRING AS |
| | NEEDED. PLAN REVIEW REQUIRES MORE SPECIFICITY. WHICH |
| | WIRING IS TO BE REPLACED AND WHICH IS TO REMAIN? NO |
| | SWITCHES OR OUTLETS ARE INDICATED AS REMAINING OR TO BE |
| | REPLACED, IF ALL ARE TO BE REPLACED THEN STATE IT. |
| | |
| | 3) A SITE PLAN LOCATING ALL METERS, DISCONNECTS, |
| | ELECTRIC PANELS, AIR CONDITIONING EQUIPMENT AND ALL |
| | OTHER RELEVANT ELECTRICAL EQUIPMENT. LABEL ALL |
| | EQUIPMENT AS APPLICABLE. IF THERE IS MORE THAN ONE, |
| | LABEL THEM ACCORDINGLY AS A, B, C ETC.. NEC 215.5 AND |
| | FBC 107.2 |
| | NOT ADDRESSED |
| | |
| | 4) PROVIDE A RISER DIAGRAM DETAILING ALL METERS, |
| | DISCONNECTS, ELECTRIC PANELS AND SUBPANELS. INCLUDE ALL |
| | CONDUIT, CONDUCTOR AND EQUIPMENT SIZES. INCLUDE ALL |
| | GROUNDING ELECTRODE SYSTEMS. INCLUDE ALL NEW PROPOSED |
| | EQUIPMENT AND SUB PANELS. THERE IS A SUBMITTAL FOR A |
| | NEW POOL INSTALLATION THAT DETAILS ADDITIONAL ELECTRIC |
| | LOADS TO BE INSTALLED. IF THIS IS A SUB PANEL, INCLUDE |
| | THIS IN THE RISER. NEC 215.5 AND FBC 107.2 |
| | NOT ADDRESSED. FLOOR PLANS DETAIL 2 ELECTRIC PANELS IN |
| | ONE STRUCTURE AND 1 IN THE OTHER. RISER DETAILS A METER |
| | AND 2 ELECTRIC PANELS. PLEASE PROVIDE A CORRECT |
| | ELECTRIC RISER DIAGRAM. 2/0 CU WIRE IS DETAILED |
| | INCORRECTLY FOR A 225 AMP PANEL. THIS WIRE HAS AN |
| | AMPACITY OF 175 AMPS. #6 CU WIRE IS DETAILED FOR A 125 |
| | AMP PANEL WITH A 100 AMP BREAKER AS OVERCURRENT |
| | PROTECTION. #6 WIRE HAS AN AMPACITY OF 65 AMPS. |
| | ELECTRIC FLOOR PLAN DOES NOT DETAIL ELECTRIC METER OR |
| | PROPOSED POOL EQUIPMENT. |
| | |
| | 5) PROVIDE ALL PANEL SCHEDULES WITH ALL ELECTRIC LOADS |
| | LISTED. NEC 215.5 AND FBC 107.2 |
| | NOT ADDRESSED. SUBMITTAL IS STILL UNCLEAR WHERE AND HOW |
| | MANY ELECTRIC PANELS EXIST. |
| | |
| | 6) PROVIDE SPECIFICATIONS FOR ALL EQUIPMENT. INCLUDE |
| | ALL AIR CONDITIONING, WATER HEATERS, PUMPS, RANGES AND |
| | OTHER ELECTRIC APPLIANCES. NEC 215.5 AND FBC 107.2 |
| | NOT ADDRESSED |
| | |
| | 7) PROVIDE AN ACCURATE LOAD CALCULATION FOR EACH PANEL. |
| | NEC 215.5 AND FBC 107.2 |
| | NOT ADDRESSED. SUBMITTAL LACKS CLARITY. SEE PRIOR |
| | COMMENTS. |
| | |
| | 8) PROVIDE AN ELECTRIC LOAD CALCULATION FOR THE ENTIRE |
| | SERVICE USING ONE OF THE TWO METHODS DESCRIBED IN NEC |
| | ARTICLE 220 (STANDARD OR OPTIONAL) DETAIL ON |
| | CALCULATION WHICH METHOD WAS USED. NEC 215.5 AND FBC |
| | 107.2 |
| | NOT ADDRESSED. SUBMITTAL LACKS CLARITY. CALCULATION |
| | METHOD IS NOT DETAILED. DETAIL ALL LOADS USED TO ARRIVE |
| | AT TOTAL GENERAL ELECTRICAL LOAD. SEE PRIOR COMMENTS. |
| | |
| | 9) PROVIDE ELECTRIC FLOOR PLANS FOR BOTH STRUCTURES. |
| | INCLUDE ALL ELECTRIC OUTLETS, SWITCHES, RECEPTACLES, |
| | APPLIANCES AND OTHER ELECTRICAL WIRING AS OUTLINED IN |
| | NEC ARTICLE 210. FBC 107.2 |
| | NOT ADDRESSED. SEE PRIOR COMMENTS. ONLY ONE SMALL |
| | APPLIANCE CIRCUIT IS DETAILED. |
| | |
| | FBC 107.2, CONSTRUCTION DOCUMENTS SHALL BE OF |
| | SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE AND |
| | EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT IT |
| | WILL CONFORM TO THE PROVISIONS OF THIS CODE AND |
| | RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS |
| | DETERMINED BY THE BUILDING OFFICIAL. |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. |
| | |
| | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2020 7TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE 2020 7TH ED. |
| | FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020 |
| | 7TH EDITION |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 |
| | 7TH EDITION |
| | FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION |
| | NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE |
| | FS = FLORIDA STATUTES |
| | |
| | V/R, |
| | |
| | MICHAEL PETERSON |
| | ELECTRICAL PLANS EXAMINER |