2023-07-17 14:50:36ELECTRIC REVIEW FAILED
 PROVIDED A WRITTEN NARRATIVE HOW THE BELOW COMMENTS
 WILL BE ADDRESSED.
 1) SITE PLAN IDENTIFYING ALL STRUCTURES. FBC 107.2 NOT
 ADDRESSED
  
 2) A NARRATIVE WORK SCOPE FOR EACH STRUCTURE. FBC 107.2
 PARTIALLY ADDRESSED. PLANS STATE REPLACE WIRING AS
 NEEDED. PLAN REVIEW REQUIRES MORE SPECIFICITY. WHICH
 WIRING IS TO BE REPLACED AND WHICH IS TO REMAIN? NO
 SWITCHES OR OUTLETS ARE INDICATED AS REMAINING OR TO BE
 REPLACED, IF ALL ARE TO BE REPLACED THEN STATE IT.
  
 3) A SITE PLAN LOCATING ALL METERS, DISCONNECTS,
 ELECTRIC PANELS, AIR CONDITIONING EQUIPMENT AND ALL
 OTHER RELEVANT ELECTRICAL EQUIPMENT. LABEL ALL
 EQUIPMENT AS APPLICABLE. IF THERE IS MORE THAN ONE,
 LABEL THEM ACCORDINGLY AS A, B, C ETC.. NEC 215.5 AND
 FBC 107.2
 NOT ADDRESSED
  
 4) PROVIDE A RISER DIAGRAM DETAILING ALL METERS,
 DISCONNECTS, ELECTRIC PANELS AND SUBPANELS. INCLUDE ALL
 CONDUIT, CONDUCTOR AND EQUIPMENT SIZES. INCLUDE ALL
 GROUNDING ELECTRODE SYSTEMS. INCLUDE ALL NEW PROPOSED
 EQUIPMENT AND SUB PANELS. THERE IS A SUBMITTAL FOR A
 NEW POOL INSTALLATION THAT DETAILS ADDITIONAL ELECTRIC
 LOADS TO BE INSTALLED. IF THIS IS A SUB PANEL, INCLUDE
 THIS IN THE RISER. NEC 215.5 AND FBC 107.2
 NOT ADDRESSED. FLOOR PLANS DETAIL 2 ELECTRIC PANELS IN
 ONE STRUCTURE AND 1 IN THE OTHER. RISER DETAILS A METER
 AND 2 ELECTRIC PANELS. PLEASE PROVIDE A CORRECT
 ELECTRIC RISER DIAGRAM. 2/0 CU WIRE IS DETAILED
 INCORRECTLY FOR A 225 AMP PANEL. THIS WIRE HAS AN
 AMPACITY OF 175 AMPS. #6 CU WIRE IS DETAILED FOR A 125
 AMP PANEL WITH A 100 AMP BREAKER AS OVERCURRENT
 PROTECTION. #6 WIRE HAS AN AMPACITY OF 65 AMPS.
 ELECTRIC FLOOR PLAN DOES NOT DETAIL ELECTRIC METER OR
 PROPOSED POOL EQUIPMENT.
  
 5) PROVIDE ALL PANEL SCHEDULES WITH ALL ELECTRIC LOADS
 LISTED. NEC 215.5 AND FBC 107.2
 NOT ADDRESSED. SUBMITTAL IS STILL UNCLEAR WHERE AND HOW
 MANY ELECTRIC PANELS EXIST.
  
 6) PROVIDE SPECIFICATIONS FOR ALL EQUIPMENT. INCLUDE
 ALL AIR CONDITIONING, WATER HEATERS, PUMPS, RANGES AND
 OTHER ELECTRIC APPLIANCES. NEC 215.5 AND FBC 107.2
 NOT ADDRESSED
  
 7) PROVIDE AN ACCURATE LOAD CALCULATION FOR EACH PANEL.
 NEC 215.5 AND FBC 107.2
 NOT ADDRESSED. SUBMITTAL LACKS CLARITY. SEE PRIOR
 COMMENTS.
  
 8) PROVIDE AN ELECTRIC LOAD CALCULATION FOR THE ENTIRE
 SERVICE USING ONE OF THE TWO METHODS DESCRIBED IN NEC
 ARTICLE 220 (STANDARD OR OPTIONAL) DETAIL ON
 CALCULATION WHICH METHOD WAS USED. NEC 215.5 AND FBC
 107.2
 NOT ADDRESSED. SUBMITTAL LACKS CLARITY. CALCULATION
 METHOD IS NOT DETAILED. DETAIL ALL LOADS USED TO ARRIVE
 AT TOTAL GENERAL ELECTRICAL LOAD. SEE PRIOR COMMENTS.
  
 9) PROVIDE ELECTRIC FLOOR PLANS FOR BOTH STRUCTURES.
 INCLUDE ALL ELECTRIC OUTLETS, SWITCHES, RECEPTACLES,
 APPLIANCES AND OTHER ELECTRICAL WIRING AS OUTLINED IN
 NEC ARTICLE 210. FBC 107.2
 NOT ADDRESSED. SEE PRIOR COMMENTS. ONLY ONE SMALL
 APPLIANCE CIRCUIT IS DETAILED.
  
 FBC 107.2, CONSTRUCTION DOCUMENTS SHALL BE OF
 SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE AND
 EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT IT
 WILL CONFORM TO THE PROVISIONS OF THIS CODE AND
 RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS
 DETERMINED BY THE BUILDING OFFICIAL.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM.
  
 CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2020 7TH ED.
 FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020
 7TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION
 NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 V/R,
  
 MICHAEL PETERSON
 ELECTRICAL PLANS EXAMINER