Plan Review Notes
Plan Review Notes For Permit 23020859
Permit Number 23020859
Review Stop M
Sequence Number 2
Notes
Date Text
2023-05-02 11:56:252ND REVIEW FMC
 PERMIT: 23020859
  
 CODES IN EFFECT: 2020
  
 FBC- FLORIDA BUILDING CODE
 FMC- FLORIDA MECHANICAL CODE
 FEC- FLORIDA ENERGY CONSERVATION
 FGC- FLORIDA FUEL GAS
 FEX- FLORIDA EXISTING BUILDING CODE
 FRC- FLORIDA RESIDENTIAL BUILDING CODE
 F.S.- FLORIDA STATUTES
 FAC- FLORIDA ACCESSIBILITY CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THE REVISED SHEET A-4 SUBMITTED THIS CYCLE SHOWS THE
 DRYER LOCATION AND NEW MINI-SPLITS. PROVIDE THE ENERGY
 CALCULATIONS FOR THESE NEW MINI-SPLITS. PROVIDE THE
 MECHANICAL EQUIPMENT SIZING CALCULATIONS FOR THESE
 MINI-SPLITS. PROVIDE THE ANCHORING DETAILS FOR THE
 MINI-SPLIT CONDENSING UNIT. PROVIDE A MECHANICAL
 DRAWING SHOWING THESE CHANGES AND THE DRYER DUCT
 INCLUDING THE SIZE AND TERMINATION LOCATION. FBC
 107.3.5
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  