| 2023-05-02 14:11:29 | ELECTRIC REVIEW FAILED |
| | |
| | 1) THIS SUBMITTAL WORK SCOPE IS VERY UNCLEAR. ONE, THIS |
| | IS FOR RENOVATION OF 2 STRUCTURES, HOWEVER ONLY ONE |
| | ELECTRIC PLAN WAS SUBMITTED. PLEASE PROVIDE THE |
| | FOLLOWING: |
| | |
| | 1) SITE PLAN IDENTIFYING ALL STRUCTURES. FBC 107.2 |
| | |
| | 2) A NARRATIVE WORK SCOPE FOR EACH STRUCTURE. FBC 107.2 |
| | |
| | 3) A SITE PLAN LOCATING ALL METERS, DISCONNECTS, |
| | ELECTRIC PANELS, AIR CONDITIONING EQUIPMENT AND ALL |
| | OTHER RELEVANT ELECTRICAL EQUIPMENT. LABEL ALL |
| | EQUIPMENT AS APPLICABLE. IF THERE IS MORE THAN ONE, |
| | LABEL THEM ACCORDINGLY AS A, B, C ETC.. NEC 215.5 AND |
| | FBC 107.2 |
| | |
| | 4) PROVIDE A RISER DIAGRAM DETAILING ALL METERS, |
| | DISCONNECTS, ELECTRIC PANELS AND SUBPANELS. INCLUDE ALL |
| | CONDUIT, CONDUCTOR AND EQUIPMENT SIZES. INCLUDE ALL |
| | GROUNDING ELECTRODE SYSTEMS. INCLUDE ALL NEW PROPOSED |
| | EQUIPMENT AND SUB PANELS. THERE IS A SUBMITTAL FOR A |
| | NEW POOL INSTALLATION THAT DETAILS ADDITIONAL ELECTRIC |
| | LOADS TO BE INSTALLED. IF THIS IS A SUB PANEL, INCLUDE |
| | THIS IN THE RISER. NEC 215.5 AND FBC 107.2 |
| | |
| | 5) PROVIDE ALL PANEL SCHEDULES WITH ALL ELECTRIC LOADS |
| | LISTED. NEC 215.5 AND FBC 107.2 |
| | |
| | 6) PROVIDE SPECIFICATIONS FOR ALL EQUIPMENT. INCLUDE |
| | ALL AIR CONDITIONING, WATER HEATERS, PUMPS, RANGES AND |
| | OTHER ELECTRIC APPLIANCES. NEC 215.5 AND FBC 107.2 |
| | |
| | 7) PROVIDE AN ACCURATE LOAD CALCULATION FOR EACH PANEL. |
| | NEC 215.5 AND FBC 107.2 |
| | |
| | 8) PROVIDE AN ELECTRIC LOAD CALCULATION FOR THE ENTIRE |
| | SERVICE USING ONE OF THE TWO METHODS DESCRIBED IN NEC |
| | ARTICLE 220 (STANDARD OR OPTIONAL) DETAIL ON |
| | CALCULATION WHICH METHOD WAS USED. NEC 215.5 AND FBC |
| | 107.2 |
| | |
| | 9) PROVIDE ELECTRIC FLOOR PLANS FOR BOTH STRUCTURES. |
| | INCLUDE ALL ELECTRIC OUTLETS, SWITCHES, RECEPTACLES, |
| | APPLIANCES AND OTHER ELECTRICAL WIRING AS OUTLINED IN |
| | NEC ARTICLE 210. FBC 107.2 |
| | |
| | FBC 107.2, CONSTRUCTION DOCUMENTS SHALL BE OF |
| | SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE AND |
| | EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT IT |
| | WILL CONFORM TO THE PROVISIONS OF THIS CODE AND |
| | RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS |
| | DETERMINED BY THE BUILDING OFFICIAL. |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. |
| | |
| | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2020 7TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE 2020 7TH ED. |
| | FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020 |
| | 7TH EDITION |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 |
| | 7TH EDITION |
| | FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION |
| | NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE |
| | FS = FLORIDA STATUTES |
| | |