| 2023-03-07 16:49:56 | ELECTRIC REVIEW FAILED |
| | |
| | 1) PROVIDE A CORRECT ELECTRIC LOAD CALCULATION FOR |
| | PANEL A. THE ELECTRIC LOAD CALCULATION SUBMITTED |
| | INCORRECTLY LISTS THE, CALCULATED DEMAND LOAD, FROM |
| | PANEL B INSTEAD OF THE ACTUAL ELECTRIC LOADS. THE |
| | CORRECT CALCULATION WILL CALCULATE ALL LOADS FOR THE |
| | MAIN SERVICE FEEDERS FROM THE METER TO PANEL A, |
| | ACCORDING TO NEC 220.40, STANDARD CALCULATION OR |
| | 220.80, OPTIONAL CALCULATION. |
| | 2) BOTH RANGES ARE LISTED AS HAVING A LOAD OF 3KW, THE |
| | MINIMUM LOAD AS PER NEC 220.55 IS 8KW. PLEASE CORRECT |
| | LOAD CALCULATIONS FOR BOTH PANEL A AND B AS APPLICABLE |
| | 3) PANEL B IS LISTED AS A 50 AMP PANEL, HOWEVER THE |
| | LOAD LISTED ON THE LOAD CALCULATION IS STATED AS |
| | 28,6886 WATTS. 28886/240= 120 AMPS. PLEASE CORRECT THE |
| | PANEL SIZE AND FEEDERS AS APPLICABLE. NEC 215.2, FEEDER |
| | CONDUCTORS SHALL HAVE AN AMPACITY NOT LESS THAN |
| | REQUIRED TO SUPPLY THE LOAD AS CALCULATED |
| | 4) PLEASE PROVIDE A WORK SCOPE AND ELECTRIC FLOOR PLAN |
| | FOR DWELLING WITH THE GARAGE. FBC 107.2 |
| | FBC 107.2, CONSTRUCTION DOCUMENTS SHALL BE OF |
| | SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE AND |
| | EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT IT |
| | WILL CONFORM TO THE PROVISIONS OF THIS CODE AND |
| | RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS |
| | DETERMINED BY THE BUILDING OFFICIAL |
| | 5) PROVIDE CORRECT ADDRESSES ON ALL PLANS FOR BOTH |
| | STRUCTURES. FBC 107.2 |
| | 6) CORRECTLY LABEL EACH ELECTRIC PANEL AS APPLICABLE. |
| | FBC 107.2 |
| | 7) PROVIDE AN ELECTRIC RISER THAT DETAILS THE CORRECT |
| | EQUIPMENT SIZES AND GROUNDING ELECTRODE SYSTEMS AS |
| | REQUIRED PER NEC 250.32 BUILDING(S) OR STRUCTURE(S) |
| | SUPPLIED BY FEEDER(S) OR BRANCH CIRCUIT(S) SHALL HAVE A |
| | GROUNDING ELECTRODE OR GROUNDING ELECTRODE SYSTEM |
| | INSTALLED |
| | 8) PLEASE DETAIL THE REQUIRED OUTDOOR RECEPTACLES AT |
| | THE FRONT AND SIDE ENTRY OF THE HOUSE AS PER NEC |
| | 210.52(E)(3) |
| | NEC 210.52(E)(3) BALCONIES, DECKS, AND PORCHES. |
| | BALCONIES, DECKS, AND PORCHES THAT ARE ATTACHED TO THE |
| | DWELLING UNIT AND ARE ACCESSIBLE FROM INSIDE THE |
| | DWELLING UNIT SHALL HAVE AT LEAST ONE RECEPTACLE OUTLET |
| | ACCESSIBLE FROM THE BALCONY, DECK, OR PORCH. |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. |
| | |
| | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2020 7TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE 2020 7TH ED. |
| | FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020 |
| | 7TH EDITION |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 |
| | 7TH EDITION |
| | FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION |
| | NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE |
| | FS = FLORIDA STATUTES |
| | |
| | V/R, |
| | |
| | MICHAEL PETERSON |
| | ELECTRICAL PLANS EXAMINER |
| | [email protected] |
| | 561-805-6746 |
| | |
| | |