| 2023-05-10 07:53:08 | 1ST REVIEW FMC |
| | PERMIT: 23020832 |
| | |
| | CODES IN EFFECT: 2020 |
| | |
| | FBC- FLORIDA BUILDING CODE |
| | FMC- FLORIDA MECHANICAL CODE |
| | FEC- FLORIDA ENERGY CONSERVATION |
| | FGC- FLORIDA FUEL GAS |
| | FEX- FLORIDA EXISTING BUILDING CODE |
| | FRC- FLORIDA RESIDENTIAL BUILDING CODE |
| | F.S.- FLORIDA STATUTES |
| | FAC- FLORIDA ACCESSIBILITY CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) THE OUTDOOR AIR CALCULATIONS DO NOT PROVIDE THE AGE |
| | OF THE STUDENTS TABLE 403.3.1.1 IDENTIFIES 2 AGE |
| | GROUPS, WHICH IS THIS EDUCATION OCCUPANCY DESIGNED |
| | FOR?. THERE IS WHAT APPEARS TO BE AN ART ROOM IN |
| | CLASSROOM 7, PROVIDE THE VENTILATION CALCULATIONS FOR |
| | THIS ROOM AS THERE SHOULD ALSO BE EXHAUST. THE READING |
| | AREA IS NOT SHOWN IN THE VENTILATION CALCULATIONS. |
| | PROVIDE A COMPLETE VENTILATION CALCULATION FOR THIS |
| | EDUCATION OCCUPANCY. USE THE OCCUPANCY CLASSIFICATION |
| | THAT MOST CLOSELY RESEMBLES THE USE OF EACH SPACE FROM |
| | TABLE 403.3.1.1. |
| | |
| | 2) PROVIDE INFORMATION ABOUT THE PIECE OF EQUIPMENT |
| | THAT IS LOCATED IN CLASSROOM 7, IS THIS A KILN? IF SO |
| | PLEASE SHOW THE REQUIRED EXHAUST FOR THIS ART ROOM. FMC |
| | TABLE 403.3.1.1 |
| | |
| | 3) ALL THE MECHANICAL DRAWINGS NEED THE ENGINEER???S |
| | DIGITAL SIGNATURE. FS 471/481 |
| | |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM. |
| | |
| | MICHAEL EDWARDS |
| | MECHANICAL EXAMINER |