| 2023-03-08 08:22:52 | 1ST REVIEW FBC-2020 PLUMBING |
| | PERMIT- 23020832 |
| | 3/7/2023 |
| | |
| | CODES IN EFFECT: |
| | FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 |
| | FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) COVER SHEET: THE PLUMBING FIXTURE SCHEDULE INDICATES |
| | A TOTAL OF 2 DRINKING FOUNTAINS PROVIDED HOWEVER TABLE |
| | 403.1 FBC P REQUIRES 5 BASED ON THE OCCUPANT LOAD OF |
| | 462 SHOWN ON SHEET A-010. PLEASE NOTE THE FOLLOWING |
| | CODE SECTIONS: |
| | |
| | SEC. 468.3.5.1 STANDARDS FBC B. |
| | EDUCATIONAL AND ANCILLARY FACILITIES SHALL BE PROVIDED |
| | WITH TOILETS, HAND WASHING FACILITIES, AND DRINKING |
| | FOUNTAINS FOR ALL OCCUPANTS, IN RATIOS AND ACCESSIBLE |
| | AS REQUIRED BY THE FLORIDA BUILDING CODE, FLORIDA LAW, |
| | AND FEDERAL REQUIREMENTS. |
| | |
| | SEC. 410.3 FBC P: WHERE DRINKING FOUNTAINS ARE |
| | REQUIRED, NOT FEWER THAN TWO DRINKING FOUNTAINS SHALL |
| | BE PROVIDED. ONE DRINKING FOUNTAIN SHALL COMPLY WITH |
| | THE REQUIREMENTS FOR PEOPLE WHO USE A WHEELCHAIR AND |
| | ONE DRINKING FOUNTAIN SHALL COMPLY WITH THE |
| | REQUIREMENTS FOR STANDING PERSONS. |
| | EXCEPTIONS: |
| | 1. A SINGLE DRINKING FOUNTAIN WITH TWO SEPARATE SPOUTS |
| | THAT COMPLIES WITH THE REQUIREMENTS FOR PEOPLE WHO USE |
| | A WHEELCHAIR AND STANDING PERSONS SHALL BE PERMITTED TO |
| | BE SUBSTITUTED FOR TWO SEPARATE DRINKING FOUNTAINS. |
| | |
| | 2) SHEETS P200 & P401 STUDENT RESTROOMS 104W.1, 104S.1, |
| | 104R.1, & 104M.1: THE S1 SINK DRAINS SHALL NOT |
| | DISCHARGE INTO THE BATHROOM HORIZONTAL WET VENTS- SEC. |
| | 912.1 FBC P. |
| | |
| | 3) P200 & P401 STUDENT RESTROOMS 104N.1 & 104K.1: NOT |
| | MORE THAN ONE THAN ONE WET-VENTED FIXTURE DRAIN SHALL |
| | DISCHARGE UPSTREAM OF THE DRY-VENTED FIXTURE DRAIN |
| | CONNECTION. THE DRAWINGS SHOW TWO WATER CLOSET (WC3) |
| | FIXTURE DRAINS CONNECTING UPSTREAM OF THE L1 DRY VENTED |
| | FIXTURE DRAIN. |
| | |
| | 4) P200 & P401: SHOW THE TOTAL DFU LOAD FOR THE 6-INCH |
| | BUILDING DRAIN- TABLE 710.1.(1) FBC P. |
| | |
| | 5) P200, P401, & P000: PLEASE ADD THE FLOOR DRAIN |
| | SPECIFICATIONS TO THE FIXTURE SCHEDULE AND INDICATE HOW |
| | TRAP SEAL PROTECTION WILL BE PROVIDED ON THE DRAWINGS- |
| | SEC. 1002.4.1 FBC P. |
| | |
| | 6) P-500 WATER HEATER DETAIL: BECAUSE THE THERMOSTAT ON |
| | THE WATER HEATER CANNOT BE THE TEMPERATURE LIMITING |
| | MEANS FOR THE HOT WATER SYSTEM, A MASTER THERMOSTATIC |
| | MIXING VALVE IS REQUIRED- SEC. 607.1.1 FBC PLEASE |
| | REVISE THE WATER HEATER DETAIL TO SHOW THE LOCATION OF |
| | THE DEVICE AND PIPING CONNECTIONS- 607.2.2. |
| | |
| | 7) P-201 & P-401: TEMPERED WATER SHALL BE DELIVERED |
| | FROM THE LAVATORIES THROUGH A WATER TEMPERATURE |
| | LIMITING DEVICE THAT CONFORMS TO ASSE 1070- SECS. 419.5 |
| | & 607.1.2 FBC P. |
| | |
| | 8) P-201 & P-401: THE 1/2-INCH HOT WATER FIXTURE SUPPLY |
| | PIPES AT THE LAVATORIES ARE EXCEEDING THEIR MAXIMUM |
| | ALLOWABLE LENGTHS OF 2FT FROM THE HOT WATER SOURCE TO |
| | THE PIPE TERMINATION. THE NEAREST SOURCE IN THIS CASE |
| | IS THE RECIRCULATION LINE- TABLE C404.5.1 FBC ENERGY. |
| | |
| | 9) A-410: THE ACCESSORIES LEGEND SHOWS THE GRAB BAR |
| | (GB-1, 2 & 3) HEIGHTS AFF TO THE CENTERLINES (CL) OF |
| | THE BARS, HOWEVER THE MEASUREMENTS SHALL BE TO THE TOPS |
| | OF THE GRIPPING SURFACES- SEC. 609.4 FBC ACC. |
| | |
| | 10) A-410: THE ACCESSORIES LEGEND SHOWS THE MOUNTING |
| | HEIGHT OF THE MIRRORS TO THE LOWER EDGES. PLEASE |
| | CORRECT TO INDICATE THE REFLECTIVE SURFACES PER SEC. |
| | 603.3 FBC ACC. |
| | |
| | 11) A-410: PLEASE SHOW THE DRINKING FOUNTAIN SPOUT |
| | HEIGHTS IN COMPLIANCE WITH SECS. 602.4 & 602.7 FBC ACC. |
| | |
| | 12) P200 & P201: THE DRINKING FOUNTAINS APPEAR TO BE |
| | PROTRUDING INTO THE CIRCULATION PATH AND NOT LOCATED IN |
| | COMPLIANCE WITH SEC. 307.2 FBC ACC. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |