| 2023-03-14 06:44:44 | 1ST REVIEW FMC | | | PERMIT: 23020832 | | | | | | CODES IN EFFECT: 2020 | | | | | | FBC- FLORIDA BUILDING CODE | | | FMC- FLORIDA MECHANICAL CODE | | | FEC- FLORIDA ENERGY CONSERVATION | | | FGC- FLORIDA FUEL GAS | | | FEX- FLORIDA EXISTING BUILDING CODE | | | FRC- FLORIDA RESIDENTIAL BUILDING CODE | | | F.S.- FLORIDA STATUTES | | | FAC- FLORIDA ACCESSIBILITY CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) SHEET M-200: NOTE 1 INDICATES THIS TO BE A 4 INCH | | | DRYER DUCT. IS THIS A DOMESTIC DRYER? PROVIDE THE | | | LENGTH OF THIS DRYER DUCT. IF THE DRYER DUCTS DEVELOPED | | | LENGTH IS MORE THAN 35 FEET PROVIDE THE MANUFACTURERS | | | INSTRUCTIONS FOR THE DRYER TO BE USED. FMC 504.8.4.2, | | | 504.8.5 | | | | | | 2) PROVIDE THE SMOKE DETECTOR DESIGN FOR THE VAVS. FMC | | | 606.2.2 | | | | | | 3) PROVIDE THE OUTDOOR AIR CALCULATIONS FOR EACH | | | OCCUPANCY CLASSIFICATION OF THIS PROJECT BASED ON THE | | | OCCUPANCY CLASSIFICATIONS AND OCCUPANT DENSITY FOUND IN | | | FMC TABLE 403.3.1.1. FMC 403.3.1.1 | | | | | | 4) ENGINEER MUST DIGITALLY SIGN THE MECHANICAL | | | DOCUMENTS. FS 471/481 | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM. | | | | | | MICHAEL EDWARDS | | | MECHANICAL EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL. 33401 | | | 561-805-6728 | | | [email protected] | | | |
|