| 2023-02-23 12:26:19 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE |
| | MARSHAL, WITH THE FOLLOWING COMMENTS: |
| | |
| | 1) THERE IS AN INDICATION ON THE APPLICATION OF 360 S |
| | ROSEMARY # 1100; HOWEVER, THE PLAN SHEETS, IWITHIN THE |
| | TITLE BLOCK, INDICATE SUITE 201 AND A SEPARATE SHEET, |
| | SUITE 401. |
| | |
| | PER NFPA 1 |
| | |
| | 1.7.12 PLANS AND SPECIFICATIONS. |
| | |
| | 1.7.12.1 THE AHJ SHALL HAVE THE AUTHORITY TO REQUIRE |
| | PLANS AND SPECIFICATIONS TO ENSURE COMPLIANCE WITH |
| | APPLICABLE CODES AND STANDARDS |
| | |
| | 1.7.12.6 PLANS SHALL BE SUBMITTED TO THE AHJ PRIOR TO |
| | THE ALTERATION OF THE MEANS OF EGRESS OR FIRE |
| | PROTECTION SYSTEMS OF ANY EXISTING BUILDING. |
| | |
| | FOR THE OFFICIAL RECORD, PLEASE PROVIDE WHICH IS |
| | CORRECT AND MAKE CORRECTIONS AS APPLICABLE. |
| | |
| | |
| | 1A) EACH SUITE SHOULD HAVE BE UNDER SEPARATE PERMITS, |
| | PLEAE REVIEW WITH THE BUILDING DEPT REQUIREMENTS. |
| | |
| | PER NFPA 1 |
| | |
| | 1.7.12 PLANS AND SPECIFICATIONS. |
| | |
| | 1.7.12.1 THE AHJ SHALL HAVE THE AUTHORITY TO REQUIRE |
| | PLANS AND SPECIFICATIONS TO ENSURE COMPLIANCE WITH |
| | APPLICABLE CODES AND STANDARDS |
| | |
| | |
| | |
| | 2) THERE IS NO INDICATION OF THE ACCESS CONTROL |
| | COMPLYING WITH THE REQUIRMENTS OF NFPA 101, CH 7, MEANS |
| | OF EGRESS. |
| | |
| | 7.2.1.5.6 DOOR HARDWARE RELEASE OF ELECTRICALLY LOCKED |
| | EGRESS |
| | DOOR ASSEMBLIES. DOOR ASSEMBLIES IN THE MEANS OF EGRESS |
| | SHALL BE |
| | PERMITTED TO BE EQUIPPED WITH APPROVED ELECTRICAL |
| | LOCKING SYSTEMS |
| | RELEASED BY THE OPERATION OF DOOR HARDWARE PROVIDED |
| | THAT ALL OF THE FOLLOWING |
| | CONDITIONS ARE MET: |
| | (1) THE HARDWARE FOR EGRESS-SIDE OCCUPANT RELEASE OF |
| | THE ELECTRICAL |
| | LOCK IS AFFIXED TO THE DOOR LEAF. |
| | (2) THE HARDWARE HAS AN OBVIOUS METHOD OF OPERATION |
| | THAT IS READILY |
| | OPERATED IN THE DIRECTION OF EGRESS UNDER ALL LIGHTING |
| | CONDITIONS. |
| | (3) THE HARDWARE IS CAPABLE OF BEING OPERATED WITH ONE |
| | HAND IN THE |
| | DIRECTION OF EGRESS. |
| | (4) OPERATION OF THE HARDWARE DIRECTLY INTERRUPTS THE |
| | POWER SUPPLY TO |
| | THE ELECTRIC LOCK AND UNLOCKS THE DOOR ASSEMBLY IN THE |
| | DIRECTION |
| | OF EGRESS. |
| | (5)* LOSS OF POWER TO THE LISTED RELEASING HARDWARE |
| | AUTOMATICALLY ELECTRICALLY |
| | UNLOCKS THE DOOR ASSEMBLY IN THE DIRECTION OF EGRESS. |
| | (6) HARDWARE FOR NEW INSTALLATIONS IS LISTED IN |
| | ACCORDANCE WITH |
| | ANSI/UL 294, STANDARD FOR ACCESS CONTROL SYSTEM UNITS. |
| | |
| | PLEASE REVIEW, ENSURE COMPLAINCE AND PROVIDE AN |
| | APPLICABLE NOTE OF ACKNOWLEDGMENT |
| | |
| | |
| | 3) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET |
| | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE |
| | ABOVE. |
| | |
| | |
| | 4) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE |
| | RE-SUBMITTAL OF THE ABOVE. |
| | |
| | |
| | PETER LEDUC |
| | FIRE MARSHAL |
| | 561-804-4709 |
| | [email protected] |
| | |