| 2023-03-01 13:24:27 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE |
| | MARSHAL, WITH THE FOLLOWING COMMENTS: |
| | |
| | 1) THERE IS AN INDICATION OF 2 EXITS; HOWEVER, THERE |
| | APPEARS TO BE SLIDING DOOR TYPES INBETWEEN THE TWO |
| | AREAS. |
| | |
| | THESE SLIDING DOORS HAVE NO INDICATORS THAT THE COMPLY |
| | WITH THE EXIT DOOR REQUIRMENTS OF NFPA 101, CH 12, NEW |
| | ASSEMBLY & CH 7, MEANS OF EGRESS. |
| | |
| | 12.2.2.2 DOORS. |
| | 12.2.2.2.1 DOORS COMPLYING WITH 7.2.1 SHALL BE |
| | PERMITTED |
| | |
| | 12.2.2.2.3 ANY DOOR IN A REQUIRED MEANS OF EGRESS FROM |
| | AN AREA HAVING |
| | AN OCCUPANT LOAD OF 100 OR MORE PERSONS SHALL BE |
| | PERMITTED TO BE PRO VIDED WITH A LATCH OR LOCK ONLY IF |
| | THE LATCH OR LOCK IS PANIC HARDWARE OR |
| | FIRE EXIT HARDWARE COMPLYING WITH 7.2.1.7, UNLESS |
| | OTHERWISE PERMITTED |
| | BY ONE OF THE FOLLOWING: |
| | (1) THIS REQUIREMENT SHALL NOT APPLY TO DELAYED-EGRESS |
| | ELECTRICAL LOCK ING SYSTEMS AS PERMITTED IN 12.2.2.2.5. |
| | (2) THIS REQUIREMENT SHALL NOT APPLY TO SENSOR-RELEASE |
| | OF ELECTRICAL |
| | LOCKING SYSTEMS AS PERMITTED IN 12.2.2.2.6 |
| | |
| | 12.2.2.2.4 LOCKING DEVICES COMPLYING WITH 7.2.1.5.5 |
| | SHALL BE PERMITTED |
| | TO BE USED ON A SINGLE DOOR OR A SINGLE PAIR OF DOORS |
| | IF BOTH OF THE FOL LOWING CONDITIONS APPLY: |
| | (1) THE DOOR OR PAIR OF DOORS SERVE AS THE MAIN EXIT |
| | AND THE ASSEMBLY |
| | OCCUPANCY HAS AN OCCUPANT LOAD NOT GREATER THAN 500. |
| | (2) ANY LATCHING DEVICES ON SUCH A DOOR(S) FROM AN |
| | ASSEMBLY OCCU PANCY HAVING AN OCCUPANT LOAD OF 100 OR |
| | MORE ARE RELEASED BY |
| | PANIC HARDWARE OR FIRE EXIT HARDWARE. |
| | |
| | 12.2.2.2.3 ANY DOOR IN A REQUIRED MEANS OF EGRESS FROM |
| | AN AREA HAVING |
| | AN OCCUPANT LOAD OF 100 OR MORE PERSONS SHALL BE |
| | PERMITTED TO BE PROVIDED WITH A LATCH OR LOCK ONLY IF |
| | THE LATCH OR LOCK IS PANIC HARDWARE OR |
| | FIRE EXIT HARDWARE COMPLYING WITH 7.2.1.7, UNLESS |
| | OTHERWISE PERMITTED |
| | BY ONE OF THE FOLLOWING: |
| | (1) THIS REQUIREMENT SHALL NOT APPLY TO DELAYED-EGRESS |
| | ELECTRICAL LOCK ING SYSTEMS AS PERMITTED IN 12.2.2.2.5. |
| | (2) THIS REQUIREMENT SHALL NOT APPLY TO SENSOR-RELEASE |
| | OF ELECTRICAL |
| | LOCKING SYSTEMS AS PERMITTED IN 12.2.2.2.6 |
| | |
| | 7.2.1.4.2* DOOR LEAF SWING DIRECTION. DOOR LEAVES |
| | REQUIRED TO BE OF |
| | THE SIDE-HINGED OR PIVOTED-SWINGING TYPE SHALL SWING IN |
| | THE DIRECTION |
| | OF EGRESS TRAVEL UNDER ANY OF THE FOLLOWING CONDITIONS: |
| | (1) WHERE SERVING A ROOM OR AREA WITH AN OCCUPANT LOAD |
| | OF 50 OR MORE, |
| | EXCEPT UNDER ANY OF THE FOLLOWING CONDITIONS: |
| | (A) DOOR LEAVES IN HORIZONTAL EXITS SHALL NOT BE |
| | REQUIRED TO SWING |
| | IN THE DIRECTION OF EGRESS TRAVEL WHERE PERMITTED BY |
| | 7.2.4.3.8.1 |
| | OR 7.2.4.3.8.2. |
| | (B) DOOR LEAVES IN SMOKE BARRIERS SHALL NOT BE REQUIRED |
| | TO SWING |
| | IN THE DIRECTION OF EGRESS TRAVEL IN EXISTING HEALTH |
| | CARE OCCUPAN CIES, AS PROVIDED IN CHAPTER 19. |
| | (2) WHERE THE DOOR ASSEMBLY IS USED IN AN EXIT |
| | ENCLOSURE, UNLESS THE |
| | DOOR OPENING SERVES AN INDIVIDUAL LIVING UNIT THAT |
| | OPENS DIRECTLY |
| | INTO AN EXIT ENCLOSURE |
| | (3) WHERE THE DOOR OPENING SERVES A HIGH-HAZARD |
| | CONTENTS AREA |
| | |
| | PLEASE PROVIDE DETAILS IN COMPLIANCE. |
| | |
| | 1A) THE 2 EXITS DOOR DO NOT INDICATE THE EXIT HARDWARE |
| | & LOCKS/LATCHES AS REQUIRED AND NOTED ABOVE AND: |
| | |
| | 12.2.2.2.3 ANY DOOR IN A REQUIRED MEANS OF EGRESS FROM |
| | AN AREA HAVING |
| | AN OCCUPANT LOAD OF 100 OR MORE PERSONS SHALL BE |
| | PERMITTED TO BE PROVIDED WITH A LATCH OR LOCK ONLY IF |
| | THE LATCH OR LOCK IS PANIC HARDWARE OR |
| | FIRE EXIT HARDWARE COMPLYING WITH 7.2.1.7, UNLESS |
| | OTHERWISE PERMITTED |
| | BY ONE OF THE FOLLOWING: |
| | (1) THIS REQUIREMENT SHALL NOT APPLY TO DELAYED-EGRESS |
| | ELECTRICAL LOCK ING SYSTEMS AS PERMITTED IN 12.2.2.2.5. |
| | (2) THIS REQUIREMENT SHALL NOT APPLY TO SENSOR-RELEASE |
| | OF ELECTRICAL |
| | LOCKING SYSTEMS AS PERMITTED IN 12.2.2.2.6 |
| | |
| | PLEASE PROVIDE DETAILS IN COMPLIANCE. |
| | |
| | |
| | 2) THERE IS NO INDICATION OF THE FLOOR FINISH THAT |
| | MEETS THE REQUIREMENTS OF NFPA 101, |
| | |
| | 12.3.3.5 INTERIOR FLOOR FINISH. |
| | 12.3.3.5.1 INTERIOR FLOOR FINISH SHALL COMPLY WITH |
| | SECTION 10.2. |
| | 12.3.3.5.2 INTERIOR FLOOR FINISH IN EXIT ENCLOSURES AND |
| | EXIT ACCESS COR RIDORS AND IN SPACES NOT SEPARATED FROM |
| | THEM BY WALLS COMPLYING WITH |
| | 12.3.6 SHALL BE NOT LESS THAN CLASS II. |
| | 12.3.3.5.3 INTERIOR FLOOR FINISH SHALL COMPLY WITH |
| | 10.2.7.1 OR 10.2.7.2, |
| | AS APPLICABLE |
| | |
| | |
| | PLEASE PROVIDE DETAILS IN COMPLIANCE. |
| | |
| | 3) THERE IS NO INDICATION OF THE CEILING & WALL FINISH |
| | THAT MEETS THE REQUIREMENTS OF NFPA 101, |
| | |
| | 12.3.3 INTERIOR FINISH. |
| | 12.3.3.1 GENERAL. INTERIOR FINISH SHALL BE IN |
| | ACCORDANCE WITH |
| | SECTION 10.2 |
| | |
| | 12.3.3.3 ASSEMBLY AREAS. INTERIOR WALL AND CEILING |
| | FINISH MATERIALS |
| | COMPLYING WITH SECTION 10.2 SHALL BE CLASS A OR CLASS B |
| | IN GENERAL |
| | ASSEMBLY AREAS HAVING OCCUPANT LOADS OF MORE THAN 300 |
| | AND SHALL BE |
| | CLASS A, CLASS B, OR CLASS C IN ASSEMBLY AREAS HAVING |
| | OCCUPANT LOADS |
| | OF 300 OR FEWER |
| | |
| | PLEASE PROVIDE DETAILS IN COMPLIANCE. |
| | |
| | |
| | |
| | 4) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET |
| | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE |
| | ABOVE. |
| | |
| | |
| | 5) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE |
| | RE-SUBMITTAL OF THE ABOVE. |
| | |
| | |
| | PETER LEDUC |
| | FIRE MARSHAL |
| | 561-804-4709 |
| | [email protected] |
| | |