| 2023-03-14 15:14:26 | ELECTRIC REVIEW FAILED |
| | 1) THE ELECTRIC LOAD CALCULATION PROVIDED IS FOR A |
| | DWELLING. THE SPACE PROPOSED IS A COMMERCIAL SPACE. |
| | PLEASE PROVIDE THE APPLICABLE ELECTRIC LOAD CALCULATION |
| | IN ACCORDANCE WITH NEC ARTICLE 220 |
| | 2) THE ELECTRIC RISER PROVIDED DETAILS 2/0 CONDUCTORS |
| | WITH AN AMPACITY OF175 AMPS AND ONLY ALLOWED A 175 AMP |
| | OVERCURRENT DEVICE. . PLEASE PROVIDE CONDUCTORS WITH |
| | AMPACITY ADEQUATE FOR A 200 AMP COMMERCIAL ELECTRIC |
| | SERVICE AS SHOWN.NEC 310.15 |
| | 3) PLEASE DETAIL NEW WIRING PROVIDED FOR NEW AIR |
| | CONDITIONING 3. IN ADDITION, ENSURE TO INCLUDE THIS |
| | LOAD IN THE CORRECTED LOAD CALCULATION. FBC 107.2 AND |
| | NEC 220 |
| | |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. |
| | |