2023-03-14 15:14:26ELECTRIC REVIEW FAILED
 1) THE ELECTRIC LOAD CALCULATION PROVIDED IS FOR A
 DWELLING. THE SPACE PROPOSED IS A COMMERCIAL SPACE.
 PLEASE PROVIDE THE APPLICABLE ELECTRIC LOAD CALCULATION
 IN ACCORDANCE WITH NEC ARTICLE 220
 2) THE ELECTRIC RISER PROVIDED DETAILS 2/0 CONDUCTORS
 WITH AN AMPACITY OF175 AMPS AND ONLY ALLOWED A 175 AMP
 OVERCURRENT DEVICE. . PLEASE PROVIDE CONDUCTORS WITH
 AMPACITY ADEQUATE FOR A 200 AMP COMMERCIAL ELECTRIC
 SERVICE AS SHOWN.NEC 310.15
 3) PLEASE DETAIL NEW WIRING PROVIDED FOR NEW AIR
 CONDITIONING 3. IN ADDITION, ENSURE TO INCLUDE THIS
 LOAD IN THE CORRECTED LOAD CALCULATION. FBC 107.2 AND
 NEC 220
  
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM.
  
 CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2020 7TH ED.
 FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020
 7TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION
 NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  