| Date |
Text |
| 2023-03-13 09:10:45 | JONATHAN BROOKS JR. |
| | BUILDING PLANS EXAMINER |
| | WORK HOURS: MONDAY - FRIDAY 7:00 AM TO 3:00 PM |
| | PHONE (561) 805-6656 |
| | EMAIL: [email protected] |
| | |
| | 1ST REVIEW: FBC 2020 7TH EDITION |
| | FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020) |
| | FBC B = FBC BUILDING |
| | FBC R = FBC RESIDENTIAL |
| | FBC EB = FBC EXISTING BUILDING |
| | FBC A = FBC ACCESSIBILITY |
| | FBC EC = FBC ENERGY CONSERVATION |
| | WPB A = CITY OF WEST PALM BEACH AMENMENTS TO THE FBC |
| | RESULTS: DENIED |
| | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT |
| | TO RESUBMIT, YOU CAN EITHER DROP OFF YOUR SUBMITTAL AT |
| | CITY HALL, OR UPLOAD CORRECTIONS TO PROJECTDOX. |
| | |
| | 1. FBC B 107.2.1. SUBMITTED MIAMI-DADE COUNTY NOA NO. |
| | 21-1229.01 SYSTEM TYPE C (1) MAXIMUM DESIGN PRESSURE |
| | -52.5 PSF. DO NOT MEET THE MINIMUM ZONE 3 DESIGN |
| | PRESSURE REQUIREMENT OF -108.17 FOR EXPOSURE CATEGORY C |
| | AREAS. GENERAL LIMITATION #9 IS SPECIFICALLY REFERRED |
| | TO IN THIS NOA. THE MAXIMUM DESIGNED PRESSURE |
| | LIMITATION LISTED SHALL BE APPLICABLE TO ALL ROOF |
| | PRESSURE ZONES (I.E. FIELD, PERIMETERS, AND CORNERS). |
| | NEITHER RATIONAL ANALYSIS, NOR EXTRAPOLATION SHALL BE |
| | PERMITTED FOR ENHANCED FASTENING AT ENHANCED PRESSURE |
| | ZONES (I.E. PERIMETERS, EXTENDED CORNERS AND CORNERS). |
| | THIS SYSTEM CAN???T BE USED. PROVIDE SYSTEM THAT MEETS |
| | OR EXCEEDS THESE REQUIREMENTS. |
| | 2. FBC EB 706.8.1 PROVIDE A DETAILED COST ESTIMATE OF |
| | THE EVALUATION AND INSTALLATION OF CONNECTIONS AT THE |
| | GABLE ENDS OR ALL CORNERS THAT WILL EXCEED 15% OF THE |
| | COST OF THE ROOF REPLACEMENT WHEN COMPLETED. |
| | |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | |