| | RESIDENTIAL (R3) THIRD BUILDING REVIEW COMMENTS |
| | CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS. |
| | PERMIT #23020774 |
| | 294 GRANADA RD |
| | |
| | |
| | PREVIOUS COMMENT: |
| | 1- REVISED CONCRETE PAD ENGINEERING UPLOADED TO |
| | PROJECTDOX ON 3/20/23 DOESN'T HAVE A DIGITAL SIGNATURE. |
| | IT SHOWS AS COPY OF THE DIGITAL SIGNATURE. NEED |
| | ORIGINAL VERIFIABLE DIGITAL SIGNATURE. |
| | |
| | RESPONSE: |
| | REPEAT COMMENT. CONCRETE PAD ENGINEERING UPLOADED WITH |
| | THE CONCRETE BRIGGS GENERATOR SPECS ON 03/24/23 IS |
| | STILL A COPY AND NOW IS FOR ANOTHER PROJECT ON 33412 |
| | ZIP CODE AND FOR ANOTHER CONTRACTOR. SEE ENGINEER'S |
| | SPECIFICATIONS ON TOP RIGHT CORNER. PROVIDE |
| | CALCULATIONS FOR CURRENT JOB. |
| | |
| | PREVIOUS COMMENT: |
| | 3. GENERATOR SPECS WERE REMOVED WHEN UPLOADING THE |
| | CONCRETE PAD ENGINEERING. ONLY THE CONCRETE PAD |
| | ENGINEERING WAS UPLOADED ON 3/20/23. NEED TO PROVIDE |
| | THE GENERATOR SPECS. |
| | |
| | RESPONSE: |
| | SEE COMMENT ABOVE AND COORDINATE. |
| | |
| | WHEN RESUBMITTING, A TRANSMITTAL LETTER LISTING THE |
| | ORIGINAL REVIEW COMMENT WITH A DESCRIPTION OF WHERE AND |
| | HOW THE COMMENT WAS ADDRESSED WILL HELP TO EXPEDITE THE |
| | REVIEW PROCESS. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |
| | PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY |
| | QUESTIONS REGARDING THESE COMMENTS, |
| | JULIO GOMEZ |
| | COMMERCIAL COMBINATION PLANS EXAMINER |
| | DEVELOPMENT SERVICES DEPARTMENT |
| | BUILDING DIVISION |
| | (561)805-6712 |